Governor Outputs (Standard / Options Qf/Qu)
The governors of the standard version are designed as three-position controllers [composed of a change-over
contact and a NO (make) contact; please refer to the description in the following chapters]. If options Qu or Qf
are implemented, they are designed as quasi-continuous governors with analog outputs [please refer to the fol-
lowing chapters]. In addition to this, further configuration screens are displayed.
Three-Position Controller Outputs (Standard)
11 12 13
Voltage / power factor
controller
Common
Higher
Lower
Voltage / power
factor controller
8
Common
Speed / power
controller
Speed / power
controller
max. 250 V AC
9 10
Lower
Higher
Figure 6-17: Three-position controller outputs
Terminal Assignment Description A
max
8 common 2.5 mm²
9 higher 2.5 mm²
10 lower
Speed/power controller
2.5 mm²
11 common 2.5 mm²
12 higher 2.5 mm²
13 lower
Voltage/power factor controller
(only for "synchronous" version)
2.5 mm²
Table 6-16: Power circuit breaker outputs - terminal assignment
Analog Controller Outputs (Options Qf/Qu)
Speed / power
controller
Voltage / cosphi
controller
A
I
0 V
0 V
A
I
A
0 V
0 V
A
0 V0 V
0 V
81211 13
A
I
0 V
0 V
A
A
I
0 V
109
0 V
A
0 V
V
V
V
V
Figure 6-18: Three-position controller outputs
Terminal Assignment Description A
max
I V
A
8 I
A
2.5 mm²
9 0 V V
A
2.5 mm²
10 0 V 0 V
Speed/power controller
2.5 mm²
11 I
A
2.5 mm²
12 0 V V
A
2.5 mm²
13 0 V 0 V
Voltage/power factor controller
(only for "synchronous" version)
2.5 mm²
Table 6-17: Power circuit breaker outputs - terminal assignment
Terminal Description A
max
A B C
93 94 95 Analog input 1 1.5 mm²
96 97 98 Analog input 2 1.5 mm²
99 100 101 Analog input 3 1.5 mm²
102 103 104 Analog input 4 1.5 mm²
Table 6-18: Analog inputs - terminal assignment