Manual 37128A GCP-20 Series - Genset Control
Page 88/190 © Woodward
Automatic
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Parameter 81
Configure
automatic YES
Configuration of automatic YES/NO
Parameters are grouped together in blocks to permit quicker navigation through the
large number of configuration screens. Selecting "YES" or "NO" has no effect if
controlling or monitoring is performed. This parameter has the following effects:
YES ..............The configuration screens in the next block are displayed and can ei-
ther be viewed ("Select" push-button) or modified ("Cursor ",
"Digit " or "Select" push-buttons).
NO................The parameters in the next block are not displayed, cannot be modi-
fied and are therefore skipped.
Load Management
NOTE
To enable the automatic start/stop function, Parameter 77 “Active power load-share” must be config-
ured to “ON”, regardless if additional generators are available for load sharing.
NOTE
To carry out an automatic start/stop of the engine, all participating controls must be configured with
the identical rated power (
Parameter 17).

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Woodward GCP-20 Series and is the answer not in the manual?

Woodward GCP-20 Series Specifications

General IconGeneral
BrandWoodward
ModelGCP-20 Series
CategoryControl Unit
LanguageEnglish

Related product manuals