Manual 37128A GCP-20 Series - Genset Control
Page 72/190 © Woodward
Parameter 4
Generator number
0
Generator number (number of the control on the CAN bus) 1 to 8
If several controls are available and these are coupled via a CAN bus, a different
number must be assigned to each control for differentiation purposes. The genera-
tor number 1 should be assigned even in the case of a single control. The control
number entered here corresponds to the control number in the program LeoPC1.
Direct Configuration
NOTE
To carry out direct configuration, you require a direct configuration cable (Part #5417-557), the
LeoPC1 1 program (supplied with the cable) and the corresponding configuration files. Please consult
the online help installed when the program is installed for a description of the LeoPC1 1 PC program
and its setup.
Remote configuration: For remote configuration the level CS2 password must be entered via the parameter
"password", otherwise, the values can only be read but not written. Entering via the CAN bus has no influence on
the displayed parameters. If the control is in code level CS0, the same level of access will be granted as described
in the previous section. The configuration via the bus is enabled for 2 hours from that point in time from the time
that the last readout of configuration was performed. After two hours the password must be entered again to ac-
cess the parameters.
WARNING
If "load conf.direct" is configured to "YES", communication via the interface with terminals X1 to X5 is
blocked. If communication is to be re-established via interface X1 to X5 after finishing the configuration
of the control (e.g. CAN bus connection via a Gateway GW 4), it must be configured to "NO"!
The direct configuration port is disabled (it is automatically switched from YES to NO) once the firing
speed has been reached. This requires any further configuration of the control to be accomplished via
the front display and push buttons or via the CAN bus interface. The de-activation of direct configura-
tion is performed as a safety precaution. If multiple systems starting simultaneously (e.g. emergency
power situation) a simultaneous switching of the generator breakers to the dead busbar is prevented.
Parameter 5
load conf.direct
YES
Direct configuration YES/NO
YES ..............Configuration via the configuration port is enabled, and any CAN
bus connection that may be available via terminals X1 to X5 is dis-
abled. The following conditions must be met in order to carry out
configuration via the configuration port:
- A connection must be established via the direct configuration cable
between the control and the PC
- The baud rate of the LeoPC1 program must be set to 9,600 Baud
- The corresponding configuration file must be used (file name:
"xxxx-xxxx-yyy-zz.asm")
NO................Configuration via the configuration port is disabled, and any avail-
able CAN bus connection via the terminals X1 to X5 is enabled.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Woodward GCP-20 Series and is the answer not in the manual?

Woodward GCP-20 Series Specifications

General IconGeneral
BrandWoodward
ModelGCP-20 Series
CategoryControl Unit
LanguageEnglish

Related product manuals