EasyManuals Logo

Woodward GCP-20 Series User Manual

Woodward GCP-20 Series
190 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #148 background imageLoading...
Page #148 background image
Manual 37128A GCP-20 Series - Genset Control
Page 148/190 © Woodward
Start Counter
Parameter 282
Start counter
set 00000
Counter; number of engine starts 0 to 32,749
The start counter is used to display how many times the engine has been started.
Following each starting attempt the start counter is increased by one. This permits
the user to display the correct number of starts if this controller is used on an older
engine, a starter is replaced, or this controller is to replace an older controller.
Only maintenance personnel should configure the start counter!
NOTE
If the engine start counter is to be changed from the factory default setting, the controller must be in
code level CS2. For safety reasons, the counter is set in a 2-step sequence.
The following sequence applies:
1. Step: Set and store the desired number of starts
2. Step: Integrate the value which has been saved by ...
-- Terminate the configuration mode and switch to automatic mode
-- Display the number of engine starts
-- Press and hold the "Digit" push-button for at least 5 seconds
kWh Counter
The kWh-counter sums up the delivered electrical power of the generator, with the greatest possible reading be-
ing 999,999 GWh. Afterwards, the kWh-counter must be reset to 0 kWh. The kWh-counter cannot be precharged
to a certain value, but can only be reset. The reset is performed as follows:
Visualize the kWh/MWh counter
Press the "Digit" button for at least 5 seconds
Current Slave Pointer
A current slave pointer, which records and stores the maximum generator current, is implemented in the control.
The display of the maximum generator current can be selected by pressing the "Message" push-button. The fol-
lowing screen appears in the display:
Parameter 283
000 000 000 000
max. Gen.current
Current slave pointer; display of the maximum generator current
The maximum generator current in each phase is displayed.
Reset: Pressing and holding the "Clear" button for 3 seconds while the current
slave pointer screen is being displayed will reset the memory.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Woodward GCP-20 Series and is the answer not in the manual?

Woodward GCP-20 Series Specifications

General IconGeneral
BrandWoodward
ModelGCP-20 Series
CategoryControl Unit
LanguageEnglish

Related product manuals