8 Adjustments
8.2.2 Tuning-less Levels Setting Procedure
8-16
8.2.2 Tuning-less Levels Setting Procedure
The procedure to use the tuning-less function is given below.
The SigmaWin+ is required to execute this function.
(1) Preparation
Confirm that the tuning-less function is enabled (Pn170.0 = 1) before you set the tuning-less levels.
(2) Operating Procedure
Use the following procedure.
1.
In the SigmaWin+ main window, click Parameters - Edit Parameters.
The Parameter Editing dialog box will appear.
CAUTION
To ensure safety, perform the tuning-less function in a state where the SERVOPACK can come to an
emergency stop at any time.