6.9 Troubleshooting without Fault Display
YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual 277
Troubleshooting
6
PID output fault
Insufficient Motor Torque
Motor Rotates After the Drive Output is Shut Off
ov or Speed Loss Occurs When Starting into a Rotating Load
Output Frequency is not as High as Frequency Reference
The frequency reference is assigned to an external
source and the signal is noisy.
Ensure that noise is not affecting the signal lines.
Separate main circuit wiring and control circuit wiring.
Use twisted-pair cables or shielded wiring for the control circuit.
Increase the analog input time filter constant (H3-13).
The cable between the drive and motor is too long.
Perform Auto-Tuning.
Reduce the length of the cable.
Cause Possible Solutions
No PID feedback input.
Check the multi-function analog input terminal settings.
Set multi-function analog input terminal A1 or A2 for PID feedback (H3-02 or H3-10 =
“B”).
A signal input to the terminal selection for PID feedback is necessary.
Check the connection of the feedback signal.
Check the various PID-related parameter settings.
No PID feedback input to the terminal causes the value detected to be 0, causing a PID fault
and the drive to operate at max frequency.
The level of detection and the target value do not
correspond with each other.
PID control keeps the difference between target and detection values at 0. Set the input
level for the values relative to one another.
Use analog input gains H3-03 or H3-11 to adjust PID target and feedback signal scaling.
Reverse drive output frequency and speed
detection. When output frequency rises, the sensor
detects a speed decrease.
Set PID output for reverse characteristics (b5-09 = “1”).
Cause Possible Solutions
Auto-Tuning has not yet been performed (required
for OLV Control).
Perform Auto-Tuning.
The control mode was changed after performing
Auto-Tuning.
Perform Auto-Tuning again.
Only Line-to-Line Resistance Auto-Tuning was
performed.
Perform Rotational Auto-Tuning.
Cause Possible Solutions
Low DC Injection Braking and the drive cannot
decelerate properly.
Adjust the DC Injection braking settings.
Increase the value of b2-02 (DC Injection Braking Current).
Increase the b2-04 (DC Injection Braking Time at Stop).
Cause Possible Solutions
The load is already rotating when the drive is trying
to start it.
Stop the motor using DC Injection braking. Restart the motor.
Increase the value of b2-03 (DC Injection Braking Time at start).
Enable Speed Search at start (b3-01 = “1”).
Set a multi-function input terminal for external Speed Search command (H1-=“61” or
“62” during restart).
Cause Possible Solutions
Upper limit for the frequency reference has been
exceeded.
Set the maximum output frequency and the upper limit for the frequency reference to more
appropriate values (E1-04 and d2-01).
The following calculation yields the upper value for the output frequency = E1-04 x d2-01
/ 100
Large load triggered Stall Prevention function
during acceleration.
Reduce the load.
Adjust the Stall Prevention level during acceleration (L3-02).
Cause Possible Solutions