EasyManua.ls Logo

YASKAWA T1000V - Page 278

YASKAWA T1000V
444 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6.9 Troubleshooting without Fault Display
278 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
Buzzing Sound from Motor at 2 kHz
Unstable Motor Speed when Using PM or IPM
Motor Does Not Operate When the RUN Button on the Digital Operator is Pressed
Motor Does Not Operate When an External Run Command is Input
Motor Stops During Acceleration or When a Load is Connected
Motor Rotates in One Direction Only
Cause Possible Solutions
Exceeded 110% of the rated output current of the
drive while operating at low speeds.
If the output current rises too high at low speeds, the carrier frequency automatically
reduces and causes a whining or buzzing sound.
If the sound is coming from the motor, disable carrier frequency derating (L8-38 = “0”).
Disabling the automatic carrier frequency derating increases the chances of an overload
fault (oL2). Switch to a larger capacity motor if oL2 faults occur too frequently.
Cause Possible Solutions
The motor code for PM (E5-01) is set incorrectly.
(Yaskawa motors only)
Set parameter E5-01 in accordance with the motor being used.
The drive is operating at less than 10% of the speed
reference.
Consult with Yaskawa about using a different type of motor when attempting to operate at
10% of the speed reference.
Motor hunting occurs.
Set and carefully adjust the following parameters in the order listed:
n8-45 (Speed Feedback Detection Suppression Gain)
n8-55 (Load Inertia for PM Motors)
C4-02 (Torque Compensation Primary Delay Time)
Hunting occurs at start. Increase the S-curve time at the start of acceleration (C2-01).
Too much current is flowing through the drive.
If using a PM motor, set the correct motor code to E5-01.
If using a specialized motor, set parameter E5- to the correct value according to the
Motor Test Report.
Cause Possible Solutions
The LOCAL/REMOTE mode is not selected
properly.
Press the LOCAL/REMOTE button to switch. The LO/RE LED should be on for LOCAL
mode.
The drive is not in drive mode. A run command will not be issued. Exit to the drive mode and cycle the run command.
The frequency reference is too low.
If the frequency reference is set below the frequency set in E1-09 (Minimum Output
Frequency), the drive will not operate.
Raise the frequency reference to at least the minimum output frequency.
Cause Possible Solutions
The LOCAL/REMOTE mode is not selected
properly.
Press the LOCAL/REMOTE button to switch. The LO/RE LED should be off for REMOTE
mode.
The drive is not in Drive Mode. A run command will not be issued. Exit to the Drive mode and cycle the run command.
The frequency reference is too low.
If the frequency reference is set below the frequency set in E1-09 (Minimum Output
Frequency), the drive will not operate.
Raise the frequency reference to at least the minimum output frequency.
Cause Possible Solution
The load is too heavy.
The limit of motor response may be reached
during rapid acceleration. This may be a result of
improper stall prevention or automatic torque boost
function adjustment.
Increase the acceleration time (C1-01) or reduce the motor load. Also, consider increasing
the motor size and/or drive size.
Cause Possible Solution
"Reverse run prohibited" is selected. If b1-04
(Reverse Prohibit Operation) is set to 1 (reverse run
prohibited), the drive will not accept a reverse run
command.
Set b1-04 = “0” to allow reverse run operation.

Table of Contents

Related product manuals