B.3 Parameter Table
322 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
b2: DC Injection Braking
Use b2 parameters to configure DC Injection Braking operation
b2-01
DC Injection Braking Start
Frequency
Sets the frequency at which DC Injection Braking starts
when Ramp to Stop (b1-03 = 0) is selected. If b2-01< E1-
09, DC Injection Braking starts at E1-09.
0.0 to 10.0
0.5
Hz
AAA 189 113
b2-02
<15>
DC Injection Braking
Current
Sets the DC Injection Braking current as a percentage of
the drive rated current.
0 to 100 50% A A A 18A 114
b2-03
<15>
DC Injection Braking Time
at Start
Sets DC Injection Braking time at start. Disabled when set
to 0.00 seconds.
0.00 to
10.00
0.00 s
<2>
AAA 18B 114
b2-04
<15>
DC Injection Braking Time
at Stop
Sets DC Injection Braking time at stop.
When b1-03 = 2, actual DC Injection time is calculated as
follows:
(b2-04) x 10 x (Output Freq)/(E1-04). When b1-03 = 0, this
parameter sets the amount of DC Injection time applied to
the motor at the end of the decel ramp. Disabled when set to
0.00.
0.00 to
10.00
0.50 s
<2>
AA 18C 114
b2-08
Magnetic Flux
Compensation Value
Sets the magnetic flux compensation as a percentage
of the no-load current value (E2-03).
0 to 1000 0% A 190 114
b2-10
DC Injection Braking
Current 2
Set as a percentage of the drive rated current.
An input terminal set for DC Injection Braking 2 (H1-
= 60) will make the drive use the current level set in b2-10
for DC Injection.
0 to 100 50% A A 1FB 114
b2-12
Short Circuit Brake Time at
Start
Sets the time for Short-Circuit brake operation at start.
Disabled when set to 0.00.
<22>
0.00 to
25.50
0.00 s A A1BA115
b2-13
Short Circuit Brake Time at
Stop
Sets the Short-Circuit brake operation time at stop. Used to
stop a motor rotating due to inertia. Disabled when set to
0.00 seconds.
<22>
0.00 to
25.50
0.50 s A A1BB115
b3: Speed Search
Use b3 parameters to configure Speed Search function operation.
b3-01
Speed Search Selection at
Start
Enables/disables the Speed Search function at start.
0: Disabled - Speed Search is not automatically performed
at start.
1: Enabled - Speed Search is automatically performed at
start.
0 to 1 0 A A A 191 118
b3-02
<15>
Speed Search Deactivation
Current
Sets the current level at which the speed is assumed to be
detected and Speed Search is ended. Set as a percentage of
the drive rated current.
0 to 200
120%
<2>
AA 192 118
b3-03
<15>
Speed Search Deceleration
Time
Sets the time constant used to reduce the output frequency
during Speed Search. Related to a change from max. output
frequency to 0.
0.1 to 10.0 2.0 s A A 193 118
b3-04
<15>
V/f Gain during Speed
Search
In order to lower the output current when performing Speed
Search, this parameter determines what percentage the V/f
ratio should be reduced. The output voltage during Speed
Search becomes V/f x b3-04.
10 to 100 100% A −− 194 119
b3-05
<15>
Speed Search Delay Time
Delays the Speed Search operation after a momentary
power loss to allow time for an external output contactor to
close.
0.0 to 100 0.2 s A A A 195 119
b3-06
<15>
Output Current 1 during
Speed Search
Sets the current injected to the motor at the beginning of
Estimation type Speed Search. Set as a factor of the motor
rated current.
0.0 to 2.0
<33> AA 196 119
b3-10
<15>
Speed Search Detection
Compensation Gain
Sets the gain which is applied to the speed detected by
Speed Estimation Speed Search before the motor is
reaccelerated. Increase this setting if ov occurs when
performing Speed Search.
1.00 to
1.20
1.05 A A 19A 119
b3-14
Bi-Directional Speed Search
Selection
Selects if Speed Search detects the motor rotation direction
during Speed Search.
0: Disabled–Frequency reference direction used
1: Enabled–Detected direction used
0,1 0 A A 19E 119
No. Name Description Range Def.
Control
Mode
Addr.
Hex
Pg.
V/f
OL
V
P
M