B.6 Defaults by Drive Model Selection (o2-04)
YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual 373
No. Description Unit Setting Range
− Model CIMR-TC − 4V0018 4V0023 4V0031 4V0038
C6-01 Duty Mode Selection −
HD ND HD ND HD ND HD ND
0 1 0 1 0 1 0 1
o2-04 Drive Model Selection Hex. 99 9A 9C 9D
E2-11
(E4-11,
T1-02)
Motor rated power kW 5.5 7.5 7.5 11.0 11.0 15.0 15.0 18.5
b3-06
Output Current 1 during Speed
Search
− 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b8-04 Energy Saving Coefficient Value − 189.5 145.38 145.38 140.88 140.88 126.26 126.26 115.74
C6-02 Carrier Frequency Selection − 31313131
E2-01
(E4-01,
T1-04)
Motor Rated Current A 9.8 13.38 13.3 19.9 19.9 26.5 26.5 32.9
E2-02
(E4-02)
Motor Rated Slip Hz 1.5 1.3 1.30 1.70 1.70 1.60 1.60 1.67
E2-03
(E4-03)
Motor No-Load Current A 2.6 4.0 4.0 5.6 5.6 7.6 7.6 7.8
E2-05
(E4-05)
Motor Line-to-Line Resistance Ω 1.595 1.152 1.152 0.922 0.922 0.550 0.550 0.403
E2-06
(E4-06)
Motor Leakage Inductance % 18.2 15.5 15.5 19.6 19.6 17.2 17.2 20.1
E2-10
(E4-10)
Motor Iron Loss for Torque
Compensation
W 193 263 263 385 385 440 440 508
E5-01 PM Motor Code Selection hex FFFF FFFF FFFF FFFF FFFF FFFF FFFF FFFF
L2-02
Momentary Power Loss Ride-
Thru Time
s0.80.8112222
L2-03
Momentary Power Loss
Minimum Baseblock Time
s 0.7 0.8 0.8 0.9 0.9 1.0 1.0 1.0
L2-04
Momentary Power Loss Voltage
Recovery Ramp Time
s 0.3 0.3 0.3 0.3 0.3 0.6 0.6 0.6
L2-05
Undervoltage Detection Level
(Uv1)
V dc 380 380 380 380 380 380 380 380
L8-02 Overheat Alarm Level °C 110 110 110 110 110 110 110 110
L8-09
Output Ground Fault Detection
Selection
− 11111111
L8-35 Installation Method Selection − 22222222
L8-38
Carrier Frequency Reduction
Selection
− 22222222
n1-03
Hunting Prevention Time
Constant
ms 10 10 10 10 10 10 10 10
n9-12 On-Delay Compensation Time ms 1.50 1.50 1.70 1.70 1.60 1.60 1.50 1.50
S6-01 DC Bus Capacity μF 480 480 590 590 960 960 1180 1180
S6-02 Motor Acceleration Time s 1.68 1.75 1.75 2.65 2.65 2.44 2.44 3.17