B.6 Defaults by Drive Model Selection (o2-04)
372 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
No. Description Unit Setting Range
− Model CIMR-TC − 4V0007 4V0009 4V0011
C6-01 Duty Mode Selection −
HD ND HD ND HD ND
0 1 0 1 0 1
o2-04 Drive Model Selection Hex. 95 96 97
E2-11
(E4-11,
T1-02)
Motor rated power kW 2.2 3.0 3.0 3.7 4.0 5.5
b3-06
Output Current 1 during Speed
Search
− 0.5 0.5 0.5 0.5 0.5 0.5
b8-04 Energy Saving Coefficient Value − 313.6 265.7 265.7 245.8 245.8 189.5
C6-02 Carrier Frequency Selection − 313131
E2-01
(E4-01,
T1-04)
Motor Rated Current A 4.2 5.7 5.7 7 7 9.8
E2-02
(E4-02)
Motor Rated Slip Hz 3 2.7 2.7 2.7 2.7 1.5
E2-03
(E4-03)
Motor No-Load Current A 1.5 1.9 1.9 2.3 2.3 2.6
E2-05
(E4-05)
Motor Line-to-Line Resistance Ω 6.495 4.360 4.360 3.333 3.333 1.595
E2-06
(E4-06)
Motor Leakage Inductance % 18.7 19 19 19.3 19.3 18.2
E2-10
(E4-10)
Motor Iron Loss for Torque
Compensation
W 77 105 105 130 130 193
E5-01 PM Motor Code Selection hex FFFF FFFF FFFF FFFF FFFF FFFF
L2-02
Momentary Power Loss Ride-
Thru Time
s 0.5 0.5 0.5 0.5 0.5 0.5
L2-03
Momentary Power Loss
Minimum Baseblock Time
s 0.5 0.5 0.5 0.6 0.6 0.7
L2-04
Momentary Power Loss Voltage
Recovery Ramp Time
s 0.3 0.3 0.3 0.3 0.3 0.3
L2-05
Undervoltage Detection Level
(Uv1)
V dc 380 380 380 380 380 380
L8-02 Overheat Alarm Level °C 100 100 100 100 100 100
L8-09
Output Ground Fault Detection
Selection
− 000000
L8-35 Installation Method Selection − 000000
L8-38
Carrier Frequency Reduction
Selection
− 111111
n1-03
Hunting Prevention Time
Constant
ms 10 10 10 10 10 10
n9-12 On-Delay Compensation Time ms 1.70 1.70 1.50 1.50 1.50 1.50
S6-01 DC Bus Capacity μF 375 375 400 400 525 525
S6-02 Motor Acceleration Time s 1.45 1.45 1.45 1.54 1.54 1.54