B.6 Defaults by Drive Model Selection (o2-04)
YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual 371
Parameter List
B
Table B.7 Three-Phase 400 V Class Drives Default Settings by Drive Model Selection
No. Description Unit Default Settings
Model CIMR-TC 4V0001 4V0002 4V0004 4V0005
C6-01 Duty Mode Selection
HD ND HD ND HD ND HD ND
0 1 0 1 0 1 0 1
o2-04 Drive Model Selection Hex. 91 92 93 94
E2-11
(E4-11,
T1-02)
Motor rated power kW 0.2 0.4 0.4 0.75 0.75 1.5 1.5 2.2
b3-06
Output Current 1 during Speed
Search
1.0 1.0 0.5 0.5 0.5 0.5 0.5 0.5
b8-04 Energy Saving Coefficient Value 713.8 576.4 576.4 447.4 447.4 338.8 338.8 313.6
C6-02 Carrier Frequency Selection 31313131
E2-01
(E4-01,
T1-04)
Motor Rated Current A 0.6 1 1 1.6 1.6 3.1 3.1 4.2
E2-02
(E4-02)
Motor Rated Slip Hz 2.5 2.9 2.9 2.6 2.6 2.5 2.5 3
E2-03
(E4-03)
Motor No-Load Current A 0.4 0.6 0.6 0.8 0.8 1.4 1.4 1.5
E2-05
(E4-05)
Motor Line-to-Line Resistance Ω 83.94 38.198 38.198 22.459 22.459 10.1 10.1 6.495
E2-06
(E4-06)
Motor Leakage Inductance % 21.9 18.2 18.2 14.3 14.3 18.3 18.3 18.7
E2-10
(E4-10)
Motor Iron Loss for Torque
Compensation
W1214142626535377
E5-01 PM Motor Code Selection hex FFFF FFFF FFFF FFFF FFFF FFFF FFFF FFFF
L2-02
Momentary Power Loss Ride-
Thru Time
s 0.1 0.1 0.1 0.1 0.2 0.2 0.3 0.3
L2-03
Momentary Power Loss
Minimum Baseblock Time
s 0.2 0.2 0.2 0.3 0.3 0.4 0.4 0.5
L2-04
Momentary Power Loss Voltage
Recovery Ramp Time
s 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3
L2-05
Undervoltage Detection Level
(Uv1)
V dc 380 380 380 380 380 380 380 380
L8-02 Overheat Alarm Level °C 110 110 110 110 110 110 90 90
L8-09
Output Ground Fault Detection
Selection
00000000
L8-35 Installation Method Selection 00000000
L8-38
Carrier Frequency Reduction
Selection
11111111
n1-03
Hunting Prevention Time
Constant
ms 10 10 10 10 10 10 10 10
n9-12 On-Delay Compensation Time ms 1.50 1.50 1.50 1.50 1.50 1.50 1.70 1.70
S6-01 DC Bus Capacity μF 55 55 55 55 250 250 350 350
S6-02 Motor Acceleration Time s 1.78 1.78 1.78 1.42 1.42 1.66 1.66 1.45