B.6 Defaults by Drive Model Selection (o2-04)
370 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
No. Description Unit Default Settings
− Model CIMR-TC − 2V0030 2V0040 2V0056 2V0069
C6-01 Duty Mode Selection −
HD ND HD ND HD ND HD ND
0 1 0 1 0 1 0 1
o2-04 Drive Model Selection Hex. 6A 6B 6D 6E
E2-11
(E4-11,
T1-02)
Motor rated power kW 5.5 7.5 7.5 11.0 11.0 15.0 15.0 18.5
b3-06
Output Current 1 during Speed
Search
− 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b8-04 Energy Saving Coefficient Value − 94.75 72.69 72.69 70.44 70.44 63.13 63.13 57.87
C6-02 Carrier Frequency Selection − 31313131
E2-01
(E4-01,
T1-04)
Motor Rated Current A 19.6 26.6 26.6 39.7 39.7 53 53 65.8
E2-02
(E4-02)
Motor Rated Slip Hz 1.5 1.3 1.3 1.7 1.7 1.6 1.6 1.67
E2-03
(E4-03)
Motor No-Load Current A 5.1 8.0 8.0 11.2 11.2 15.2 15.2 15.7
E2-05
(E4-05)
Motor Line-to-Line Resistance Ω 0.399 0.288 0.288 0.230 0.230 0.138 0.138 0.101
E2-06
(E4-06)
Motor Leakage Inductance % 18.2 15.5 15.5 19.5 19.5 17.2 17.2 15.7
E2-10
(E4-10)
Motor Iron Loss for Torque
Compensation
W 172 262 262 245 245 272 272 505
E5-01 PM Motor Code Selection hex FFFF FFFF FFFF FFFF FFFF FFFF FFFF FFFF
L2-02
Momentary Power Loss Ride-
Thru Time
s 1 1 1.0 1.0 2.0 2.0 2.0 2.0
L2-03
Momentary Power Loss
Minimum Baseblock Time
s 0.7 0.8 0.8 0.9 0.9 1.0 1.0 1.0
L2-04
Momentary Power Loss Voltage
Recovery Ramp Time
s 0.3 0.3 0.3 0.3 0.3 0.3 0.6 0.6
L2-05
Undervoltage Detection Level
(Uv1)
V dc 190 190 190 190 190 190 190 190
L8-02 Overheat Alarm Level °C 115 115 121 121 120 120 120 120
L8-09
Output Ground Fault Detection
Selection
− 11111111
L8-35 Installation Method Selection − 22222222
L8-38
Carrier Frequency Reduction
Selection
− 22222222
n1-03
Hunting Prevention Time
Constant
ms 10 10 10 10 10 10 10 10
n9-12 On-Delay Compensation Time ms 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50
S6-01 DC Bus Capacity μF 2220 2220 2670 2670 3600 3600 4980 4980
S6-02 Motor Acceleration Time s 1.68 1.75 1.75 2.65 2.65 2.44 2.44 3.17