B.6 Defaults by Drive Model Selection (o2-04)
YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual 369
No. Description Unit Default Settings
− Model CIMR-TC − 2V0010 2V0012 2V0020
C6-01 Duty Mode Selection −
HD ND HD ND HD ND
0 1 0 1 0 1
o2-04 Drive Model Selection Hex. 65 66 68
E2-11
(E4-11,
T1-02)
Motor rated power kW 1.5 2.2 2.2 3.0 3.7 5.5
b3-06 Output Current 1 during Speed Search − 0.5 0.5 0.5 0.5 0.5 0.5
b8-04 Energy Saving Coefficient Value − 169.4 156.8 156.8 136.4 122.9 94.75
C6-02 Carrier Frequency Selection − 313131
E2-01
(E4-01,
T1-04)
Motor Rated Current A 6.2 8.5 8.5 11.4 14 19.6
E2-02
(E4-02)
Motor Rated Slip Hz 2.6 2.9 2.9 2.7 2.73 1.5
E2-03
(E4-03)
Motor No-Load Current A 2.8 3.0 3.0 3.7 4.5 5.1
E2-05
(E4-05)
Motor Line-to-Line Resistance Ω 1.997 1.601 1.601 1.034 0.771 0.399
E2-06
(E4-06)
Motor Leakage Inductance % 18.5 18.4 18.4 19 19.6 18.2
E2-10
(E4-10)
Motor Iron Loss for Torque
Compensation
W53777791112172
E5-01 PM Motor Code Selection hex 0005 0005 0006 0006 0008 0008
L2-02 Momentary Power Loss Ride-Thru Time s 0.3 0.3 0.5 0.5 1 1
L2-03
Momentary Power Loss Minimum
Baseblock Time
s 0.4 0.5 0.5 0.5 0.6 0.7
L2-04
Momentary Power Loss Voltage
Recovery Ramp Time
s 0.3 0.3 0.3 0.3 0.3 0.3
L2-05 Undervoltage Detection Level (Uv1) V dc 190 190 190 190 190 190
L8-02 Overheat Alarm Level °C 100 100 100 100 110 110
L8-09 Output Ground Fault Detection Selection − 000000
L8-35 Installation Method Selection − 000000
L8-38 Carrier Frequency Reduction Selection − 111111
n1-03 Hunting Prevention Time Constant ms 10 10 10 10 10 10
n9-12 On-Delay Compensation Time ms 1.80 1.80 1.80 1.80 1.60 1.60
S6-01 DC Bus Capacity μF 800 800 1100 1100 2100 2100
S6-02 Motor Acceleration Time s 1.66 1.45 1.45 1.45 1.54 1.68