B.6 Defaults by Drive Model Selection (o2-04)
368 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
Table B.6 Three-Phase, 200 V Class Drives Default Settings by Drive Model Selection
No. Description Unit Default Settings
− Model CIMR-TC − 2V0001 2V0002 2V0004 2V0006
C6-01 Duty Mode Selection −
HD ND HD ND HD ND HD ND
0 1 0 1 0 1 0 1
o2-04 Drive Model Selection Hex. 60 61 62 63
E2-11
(E4-11,
T1-02)
Motor rated power kW 0.1 0.2 0.2 0.4 0.4 0.75 0.75 1.1
b3-06 Output Current 1 during Speed Search − 1.0 1.0 1.0 1.0 1.0 1.0 0.5 0.5
b8-04 Energy Saving Coefficient Value − 481.7 356.9 356.9 288.2 288.2 223.7 223.7 196.6
C6-02 Carrier Frequency Selection − 41414141
E2-01
(E4-01,
T1-04)
Motor Rated Current A 0.6 1.1 1.1 1.9 1.9 3.3 3.3 4.9
E2-02
(E4-02)
Motor Rated Slip Hz 2.5 2.6 2.6 2.9 2.9 2.5 2.5 2.6
E2-03
(E4-03)
Motor No-Load Current A 0.4 0.8 0.8 1.2 1.2 1.8 1.8 2.3
E2-05
(E4-05)
Motor Line-to-Line Resistance Ω 35.98 20.56 20.56 9.842 9.842 5.156 5.156 3.577
E2-06
(E4-06)
Motor Leakage Inductance % 21.6 20.1 20.1 18.2 18.2 13.8 13.8 18.5
E2-10
(E4-10)
Motor Iron Loss for Torque
Compensation
W 6 11 11 14 14 26 26 38
E5-01 PM Motor Code Selection hex FFFF FFFF FFFF FFFF 0002 0002 0003 0003
L2-02
Momentary Power Loss Ride-Thru
Time
s 0.1 0.1 0.1 0.1 0.1 0.1 0.2 0.2
L2-03
Momentary Power Loss Minimum
Baseblock Time
s 0.2 0.2 0.2 0.2 0.2 0.3 0.3 0.4
L2-04
Momentary Power Loss Voltage
Recovery Ramp Time
s 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3
L2-05 Undervoltage Detection Level (Uv1) V dc 190 190 190 190 190 190 190 190
L8-02 Overheat Alarm Level °C 110 110 110 110 115 115 100 100
L8-09
Output Ground Fault Detection
Selection
− 00000000
L8-35 Installation Method Selection − 00000000
L8-38 Carrier Frequency Reduction Selection − 11111111
n1-03 Hunting Prevention Time Constant ms 10 10 10 10 10 10 10 10
n9-12 On-Delay Compensation Time ms 2.50 2.50 2.50 2.50 2.50 2.50 2.50 2.50
S6-01 DC Bus Capacity μF 220 220 220 220 220 220 330 330
S6-02 Motor Acceleration Time s 1.78 1.78 1.78 1.78 1.78 1.42 1.42 1.42