B.7 E5-01 (PM Motor Code Selection) Dependent Parameters
376 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
Table B.11 400 V, 1750 rpm Type Yaskawa SSR1 Series Motor
Par. Description Unit Default Settings
E5-01
PM Motor Code Selection − 1232 1233 1235 1236 1238
Voltage class − 400 Vac 400 Vac 400 Vac 400 Vac 400 Vac
Rated power − 0.4 kW 0.75 kW 1.5 kW 2.2 kW 3.7 kW
Rated speed r/min 1750 1750 1750 1750 1750
E5-02 Motor Rated Power kW 0.4 0.75 1.5 2.2 3.7
E5-03 Motor Rated Current A 0.83 1.49 2.75 4.05 6.80
E5-04 Number of Motor Poles – 6 6 6 6 6
E5-05 Motor Stator Resistance W 32.932 9.136 6.004 3.297 1.798
E5-06 Motor d-Axis Inductance mH 219.36 92.08 68.32 40.39 32.93
E5-07 Motor q-Axis Inductance mH 256.40 119.56 85.56 48.82 37.70
E5-09 Motor Induction Voltage Constant 1 mVs/rad 466.0 459.0 501.8 485.7 498.7
E5-24 Motor Induction Voltage Constant 2 mV/(r/min) 0.0 0.0 0.0 0.0 0.0
E1-04 Maximum Output Frequency Hz 87.5 87.5 87.5 87.5 87.5
E1-05 Maximum Voltage V 380.0 380.0 380.0 380.0 380.0
E1-06 <1> Base Frequency Hz 87.5 87.5 87.5 87.5 87.5
E1-09 <2> Minimum Output Frequency Hz 4.4 4.4 4.4 4.4 4.4
n8-49
d-Axis Current for High Efficiency
Control
% –7.2 –10.7 –11.1 –8.9 –7.9
S6-02 Motor Acceleration Time s 0.092 0.076 0.051 0.066 0.075
Par. Description Unit Default Settings
E5-01
PM Motor Code Selection − 123A 123B 123D 123E
Voltage class − 400 Vac 400 Vac 400 Vac 400 Vac
Rated power − 5.5 kW 7.5 kW 11 kW 15 kW
Rated speed r/min 1750 1750 1750 1750
E5-02 Motor Rated Power kW 5.5 7.5 11.0 15
E5-03 Motor Rated Current A 9.90 13.10 19.9 26.4
E5-04 Number of Motor Poles – 6 6 6 6
E5-05 Motor Stator Resistance W 0.982 0.786 0.368 0.263
E5-06 Motor d-Axis Inductance mH 22.7 16.49 13.38 10.51
E5-07 Motor q-Axis Inductance mH 26.80 23.46 16.99 12.77
E5-09 Motor Induction Voltage Constant 1 mVs/rad 498.0 541.7 508.7 531.9
E5-24 Motor Induction Voltage Constant 2 mV/(r/min) 0.0 0.0 0.0 0.0
E1-04 Maximum Output Frequency Hz 87.5 87.5 87.5 87.5
E1-05 Maximum Voltage V 380.0 380.0 380.0 380.0
E1-06 <1>
<1> Default setting value varies by the drive model (o2-04).
<2> Default setting is 75% of the drive rated current.
Base Frequency Hz 87.5 87.5 87.5 87.5
E1-09 <2> Minimum Output Frequency Hz 4.4 4.4 4.4 4.4
n8-49
d-Axis Current for High Efficiency
Control
% –10.2 –17.4 –15.8 –12.6
S6-02 Motor Acceleration Time s 0.083 0.077 0.084 0.102