4.3 The Drive and Programming Modes
80 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
■ Drive Mode Details
The following actions are possible in the Drive Mode:
• Run and stop the drive.
• Monitor the operation status of the drive (frequency reference, output frequency, output current, output voltage, etc.).
• View information on an alarm.
• View a history of alarms that have occurred.
Note: Select "Drive Mode" when running. The mode can be switched to any mode (program mode, etc.) other than drive mode while
the drive is stopped. However, the drive cannot be operated in other modes. Return the mode to "Drive Mode" after completing
periodic inspection.
Figure 4.4 illustrates changing the default frequency reference of F 0.00 (0 Hz) to F 6.00 (6 Hz) while in Drive Mode.
This example assumes the drive is set to LOCAL.
Figure 4. 4
Figure 4.4 Setting the Frequency Reference while in Drive Mode
Programming
Mode
Verify Function
Lists all parameters that have been edited or changed from default settings. Refer to
Verifying Parameter Changes: Verify Menu on page 82.
Setup
A select list of parameters necessary to get the drive operational quickly. Refer to The
Setup Group within the Programming Mode on page 81.
Parameter Setting
Allows the user to access and edit all parameter settings. Refer to Parameter List on
page 317.
Auto-Tuning
Motor parameters are calculated and set automatically. Refer to Auto-Tuning on
page 88.
Drive Mode
Frequency Reference
Returns to the frequency reference display screen.
STOP
Frequency reference
display at power up
Press to select LOCAL
Press until the frequency
reference becomes 6 Hz
Press to select the
digit to the right