No. Item Page(s)
24 Use twisted-pair line for all drive control circuit wiring. 110
25
Ground the shields of shielded wiring to the GND terminal.
110
26 For 3-Wire sequence, set parameters for multi-function contact input terminals S1 – S8, and wire control circuits.
27 Properly wire any option cards. 110
28 Check for any other wiring mistakes. Only use a multimeter to check wiring.
29 Properly fasten drive control circuit terminal screws. 98
30 Pick up all wire clippings.
31 Ensure that no frayed wires on the terminal block are touching other terminals or connections.
32 Properly separate control circuit wiring and main circuit wiring.
33 Analog signal line wiring should not exceed 50 m (164 ft.).
34 Safe Disable input wiring should not exceed 30 m (98.5 ft.). 672
35 Verify the logic of Safety Monitor Output Signal (DM+, DM-).
36
Disconnect the internal EMC filter by moving the SW screw to the OFF position for floating, impedance grounded, or asymmetrically grounded
networks.
120
37
Properly wire the control signal lines to Module Communications Connector port CN500 of drive models 4o0720 to 4o0930, and Module
Communications Connector port CN500 of the harmonic filter module.
112
38
The cable between drive models 4o0720 to 4o0930 and harmonic filter module should not exceed 5 m (16.4 ft.).
3.15 Wiring Checklist
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
131
3
Electrical Installation