Register No. Contents
000FH
Control Selection Setting
bit 0 Reserved
bit 1 PID Setpoint Input
bit 2 Torque reference / torque limit input (enables the setting from MEMOBUS/Modbus)
bit 3 Torque compensation input (enables the setting from MEMOBUS/Modbus)
bit 4 to B Reserved
bit C Enable Terminal S5 Input for Broadcast Data
bit D Enable Terminal S6 Input for Broadcast Data
bit E Enable Terminal S7 Input for Broadcast Data
bit F Enable Terminal S8 Input for Broadcast Data
0010H to 001AH Reserved
001BH Analog Monitor Option AO-A3 Analog Output 1 (10 V/4000 H)
001CH Analog Monitor Option AO-A3 Analog Output 2 (10 V/4000 H)
001DH Digital Output Option DO-A3 Output (Binary)
001EH to 001FH Reserved
u
Monitor Data
Monitor data can be read only.
Register No. Contents
0020H
Drive Status 1
bit 0 During Run
bit 1 During Reverse
bit 2 Drive Ready
bit 3 Fault
bit 4 Data Setting Error
bit 5 Multi-Function Contact Output 1 (terminal M1-M2)
bit 6 Multi-Function Contact Output 2 (terminal M3-M4)
bit 7 Multi-Function Contact Output 3 (terminal M5-M6)
bit 8 to bit D Reserved
bit E When ComRef has been enabled
bit F When ComCtrl has been enabled
C.9 MEMOBUS/Modbus Data Table