No. Parameter Name Setting Range Default
F6-59 DeviceNet Power Scaling -15 to 15 0
F6-60 DeviceNet Voltage Scaling -15 to 15 0
F6-61 DeviceNet Time Scaling -15 to 15 0
Setting
The monitor value in the AC/DC Drive Object 2AH is calculated by:
AC/DC Drive Object 2AH Monitor = Drive Value × 2
Scaling
Example:
If the drive output frequency monitor (U1-02) is 5.00 and the scaling is set to F6-56 = 6, then the value in the AC/DC Drive
Object 2AH, Instance 1, Attribute 7 would be 500 × 2
6
= 32000.
n
F6-62: DeviceNet Heartbeat Interval
Sets the heartbeat interval for DeviceNet communications. A setting of 0 disables the heartbeat function.
No. Parameter Name Setting Range Default
F6-62 DeviceNet Heartbeat Interval 0 to 10 0
n
F6-63: DeviceNet Network MAC ID
Displays the MAC ID assigned to the drive. F6-63 is used only as a monitor.
No. Parameter Name Setting Range Default
F6-63 DeviceNet Network MAC ID 0 to 63 (read only) 63
n
F6-64 to F6-71: Dynamic Assembly Parameters (Reserved)
n
F7-01 to F7-04: IP Address 1 to 4
Sets the significant octet of network static IP address.
n
F7-05 to F7-08: Subnet Mask 1 to 4
Sets the significant octet of network static Subnet Mask.
n
F7-09 to F7-12: Gateway Address 1 to 4
Sets the significant octet of network Gateway address.
u
Modbus TCP/IP Parameters
Parameters F7-01 through F7-16, U6-80 through U6-93, U6-98, and U6-99 set up the drive to operate on a Modbus TCP/IP
network.
For details on parameter settings, refer to the YASKAWA AC Drive 1000-Series Option Modbus TCP/IP Installation Manual
and Technical Manual.
u
PROFINET Parameters
Parameters F7-01 through F7-15, F7-17 through F7-42, U6-80 through U6-93, U6-98, and U6-99 set up the drive to operate
on a PROFINET network.
For details on parameter settings, refer to the YASKAWA AC Drive 1000-Series Option PROFINET Installation Manual and
Technical Manual.
u
EtherNet/IP Parameters
Parameters F7-01 through F7-15, F7-17 through F7-42, U6-80 through U6-93, U6-98, and U6-99 set up the drive to operate
on an EtherNet/IP network.
For details on parameter settings, refer to the YASKAWA AC Drive 1000-Series Option EtherNet/IP Installation Manual and
Technical Manual.
5.6 F: Option Settings
276
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual