o4: Maintenance Monitor Settings
No.
(Addr.
Hex)
Name LCD Display Description Values Page
o4-01
(050B)
Cumulative Operation
Time Setting
DrvElapsTimeCnt
All Modes
Sets the value for the cumulative operation time of the drive in
units of 10 h.
Default: 0
Min.: 0
Max.: 9999
348
o4-02
(050C)
Cumulative Operation
Time Selection
ElapsTimeCntSet
0: Power-On Time
1: Running Time
All Modes
0: Logs power-on time
1: Logs operation time when the drive output is active (output
operation time).
Default: 0
Range: 0, 1
348
o4-03
(050E)
Cooling Fan Operation
Time Setting
FanElapsTimeCn
All Modes
Sets the value of the fan operation time monitor U4-03 in units
of 10 h.
Default: 0
Min.: 0
Max.: 9999
348
o4-05
(051D)
Capacitor Maintenance
Setting
BusCap Maint Set
All Modes
Sets the value of the Maintenance Monitor for the capacitors. See
U4-05 to check when the capacitors may need to be replaced.
Default: 0%
Min.: 0
Max.: 150
348
o4-07
(0523)
DC Bus Pre-Charge
Relay Maintenance
Setting
ChrgCircMaintSet
All Modes
Sets the value of the Maintenance Monitor for the soft charge
bypass relay. See U4-06 to check when the bypass relay may need
to be replaced.
Default: 0%
Min.: 0
Max.: 150
349
o4-11
(0510)
U2, U3 Initialization
Fault Data Init
0: Disabled
1: Enabled
All Modes
0: U2-oo and U3-oo monitor data is not reset when the drive
is initialized using A1-03.
1: U2-oo and U3-oo monitor data is reset when the drive is
initialized using A1-03. Parameter is automatically reset to 0.
Default: 0
Range: 0, 1
349
o4-12
(0512)
kWh Monitor
Initialization
kWh Monitor Init
0: No Reset
1: Reset
All Modes
0: No action
1: Reset kWh data
Default: 0
Range: 0, 1
349
o4-13
(0528)
Number of Run
Commands Counter
Initialization
Run Counter Init
0: No Reset
1: Reset
All Modes
0: U4-02 monitor data is not reset when the drive is initialized
using A1-03.
1: U4-02 monitor data is reset when the drive is initialized using
A1-03. Parameter is automatically reset to 0.
Default: 0
Range: 0, 1
349
o4-19
(113A)
Power Unit Price Energy Price/kWh
All Modes
Sets the price per 1 kWh to calculate the power rate displayed for
total consumed power (U9-07 to U9-10) and total regenerated
power (U9-11 to U9-14).
Default: 000.00
Min.: 000.00
Max.: 650.00
349
B.12 o: Operator-Related Settings
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
565
B
Parameter List