No.
(Addr.
Hex)
Name Description
Analog
Output Level
Unit
U1-21
(0077)
AI-A3 Terminal V1
Input Voltage Monitor
AI Opt Ch1 Level
All Modes
Displays the input voltage to terminal V1 on analog input card
AI-A3.
10 V: 100%
(-10 to +10 V)
0.1%
U1-22
(072A)
AI-A3 Terminal V2
Input Voltage Monitor
AI Opt Ch2 Level
All Modes
Displays the input voltage to terminal V2 on analog input card
AI-A3.
10 V: 100%
(-10 to +10 V)
0.1%
U1-23
(072B)
AI-A3 Terminal V3
Input Voltage Monitor
AI Opt Ch3 Level
All Modes
Displays the input voltage to terminal V3 on analog input card
AI-A3.
10 V: 100%
(-10 to +10 V)
0.1%
U1-24
(007D)
Input Pulse Monitor Term RP Inp Freq
All Modes
Displays the frequency to pulse train input terminal RP.
Determined by
H6-02
1 Hz
U1-25
(004D)
Software Number
(Flash)
CPU 1 SW Number
All Modes
FLASH ID
No signal output
available
U1-26
(005B)
Software No. (ROM) CPU 2 SW Number
All Modes
ROM ID
No signal output
available
U1-54
(1083)
Drive Input Power
Voltage Effective Value
PowerSupply Volt
All Modes
Displays the effective value of the drive input power voltage.
200 V class
10 V: 400 V
400 V class
10 V: 800 V
1 V
U1-58
(1087)
Power Supply
Frequency
PoweSupply Freq
All Modes
Displays the frequency of the drive input power supply.
10 V: Rated
frequency
0.1 Hz
U1-72
(1095)
Input Power Supply
Information
Power Supply Sts
All Modes
Displays information on the input power supply.
U1
-
72=
00000000
Bit 0: AUv reset. (0: Not completed, 1: Reset)
Bit 1: PF reset (0: Not completed, 1: Reset)
Bit 2: Rated frequency detection
(0: Not completed, 1: Completed)
Bit 3: Phase order detection
(0: Not completed, 1: Completed)
Bit 4: Power supply established
(0: Not completed, 1: Completed)
Bit 5: Fdv detection (0: Not detected, 1: Detected)
Bit 6: PF detection (0: Not detected, 1: Detected)
Bit 7: Reserved.
No signal output
available
<1> Display is in the following units:
2o0028, 2o0042, and 4o0011 to 4o0027: 0.01 A units
2o0054 to 2o0248 and 4o0034 to 4o0720: 0.1 A units
4o0900 and 4o0930: 1 A units
<2> The values of U1-03, U2-05, and U4-13 are displayed on the digital operator in units of amperes. When those monitors are checked using
MEMOBUS/Modbus communications, the monitor values in MEMOBUS/Modbus communications are displayed as: numeric value / 8192 × drive
rated current (A) from the condition “192 (maximum value) = drive rated current (A)”
<3> Values shown are specific to 200 V class drives. Double the value for 400 V class drives.
<4> In V/f and V/f w/PG control modes, 10 V = default value of E2-11. In OLV, CLV control modes, 10 V = setting value of E2-11 (kW). OLV/PM,
AOLV/PM, and CLV/PM control modes, 10 V = setting value of E5-02.
<5> Display is in the following units:
2o0028, 2o0042, and 4o0011 to 4o0027: 0.01 kW units
2o0054 to 2o0248 and 4o0034 to 4o0930: 0.1 kW units
u
U2: Fault Trace
No.
(Addr.
Hex)
Name LCD Display Description
Analog
Output Level
Unit
U2-01
(0080)
Current Fault Current Fault
All Modes
Displays the current fault.
No signal output
available
U2-02
(0081)
Previous Fault Last Fault
All Modes
Displays the previous fault.
No signal output
available
B.15 U: Monitors
574
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual