EasyManua.ls Logo

YASKAWA U1000 - Page 573

YASKAWA U1000
706 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
No.
(Addr.
Hex)
Name Description
Analog
Output Level
Unit
U1-11
(004A)
Output Terminal Status Output Term Sts
All Modes
Displays the output terminal status.
U1
-
11=
00000000
Multi-Function
Digital Output
(terminal MD-ME-MF)
Digital Output
(terminal M1-M2)
Digital Output
(terminal M3-M4)
Multi-Function
Multi-Function
Not Used
Fault Relay
(terminal MA-MC closed
MA/MB-MC open)
1
1
1
1
0
No signal output
available
U1-12
(004B)
Drive Status Int Ctl Sts 1
All Modes
Displays the drive operation status.
U1
-
12=
00000000
During run
During zero-speed
During REV
During fault reset
signal input
During speed agree
Drive ready
During alarm
detection
During fault detection
1
1
1
1
1
1
1
1
No signal output
available
U1-13
(004E)
Terminal A1 Input Level Term A1 Level
All Modes
Displays the signal level to analog input terminal A1.
10 V: 100%
(-10 to +10 V)
0.1%
U1-14
(004F)
Terminal A2 Input Level Term A2 Level
All Modes
Displays the signal level to analog input terminal A2.
10 V: 100%
(-10 to +10 V)
0.1%
U1-15
(0050)
Terminal A3 Input Level Term A3 Level
All Modes
Displays the signal level to analog input terminal A3.
10 V: 100%
(-10 to +10 V)
0.1%
U1-16
(0053)
Output Frequency after
Soft Starter
SFS Output
All Modes
Displays output frequency with ramp time and S-curves. Units
determined by o1-03.
10 V: Max
frequency
(-10 to +10 V)
0.01 Hz
U1-17
(0058)
DI-A3 Input Status DI Opt Status
All Modes
Displays the reference value input from the DI-A3 option card.
Display will appear in hexadecimal as determined by the digital
card input selection in F3-01.
3FFFF: Set (1 bit) + sign (1 bit) + 16 bit
No signal output
available
U1-18
(0061)
oPE Fault Parameter OPE Error Code
All Modes
Displays the parameter number that caused the oPE02 or oPE08
operation error.
No signal output
available
U1-19
(0066)
MEMOBUS/Modbus
Error Code
Transmit Err
All Modes
Displays the contents of a MEMOBUS/Modbus error.
U1
-
19=
00000000
CRC Error
Data Length Error
Not Used
Parity Error
Overrun Error
Framing Error
Timed Out
Not Used
1
1
0
1
1
1
1
0
No signal output
available
B.15 U: Monitors
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual