YASKAWA U1000 - H5: Memobus;Modbus Serial Communication

YASKAWA U1000
706 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
No.
(Addr.
Hex)
Name LCD Display Description Values Page
H4-07
(0423)
Multi-Function Analog
Output Terminal FM
Signal Level Selection
Term FM Lvl Sel
0: 0-10 VDC
1: -10 +10 VDC
2: 4-20 mA
All Modes
0: 0 to 10 V
1: -10 to 10 V
2: 4 to 20 mA
Default: 0
Range: 0 to 2
305
H4-08
(0424)
Multi-Function Analog
Output Terminal AM
Signal Level Selection
Term AM Lvl Sel
0: 0-10 VDC
1: -10 +10 VDC
2: 4-20 mA
All Modes
0: 0 to 10 V
1: -10 to 10 V
2: 4 to 20 mA
Default: 0
Range: 0 to 2
305
u
H5: MEMOBUS/Modbus Serial Communication
Note: Restart the drive to enable MEMOBUS/Modbus communication settings.
No.
(Addr.
Hex)
Name LCD Display Description Values Page
H5-01
(0425)
<1>
Drive Node Address Serial Comm Adr
All Modes
Selects drive station node number (address) for MEMOBUS/
Modbus terminals R+, R-, S+, S-. Cycle power for the setting
to take effect.
Default: 1F (Hex)
Min.: 0
Max.: FFH
617
H5-02
(0426)
Communication Speed
Selection
Serial Baud Rate
0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19.2 kbps
5: 38.4 kbps
6: 57.6 kbps
7: 76.8 kbps
8: 115.2 kbps
All Modes
0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19200 bps
5: 38400 bps
6: 57600 bps
7: 76800 bps
8: 115200 bps
Note: Cycle power for the setting to take effect.
Default: 3
Range: 0 to 8
617
H5-03
(0427)
Communication Parity
Selection
Serial Com Sel
0: No Parity
1: Even Parity
2: Odd Parity
All Modes
0: No parity
1: Even parity
2: Odd parity
Note: Cycle power for the setting to take effect.
Default: 0
Range: 0 to 2
617
H5-04
(0428)
Stopping Method after
Communication Error
(CE)
Serial Fault Sel
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
All Modes
0: Ramp to stop
1: Coast to stop
2: Fast Stop
3: Alarm only
Default: 3
Range: 0 to 3
617
H5-05
(0429)
Communication Fault
Detection Selection
Serial Flt Dtct
0: Disabled
1: Enabled
All Modes
0: Disabled
1: Enabled. If communication is lost for more than two seconds,
a CE fault will occur.
Default: 1
Range: 0, 1
618
H5-06
(042A)
Drive Transmit Wait
Time
Transmit WaitTIM
All Modes
Set the wait time between receiving and sending data.
Note: Cycle power for the setting to take effect.
Default: 5 ms
Min.: 5
Max.: 65
618
H5-07
(042B)
RTS Control Selection
RTS Control Sel
0: Disabled
1: Enabled
All Modes
0: Disabled. RTS is always on.
1: Enabled. RTS turns on only when sending.
Note: Cycle power for the setting to take effect.
Default: 1
Range: 0, 1
618
H5-09
(0435)
Communication Fault
Detection Time
CE Detect Time
All Modes
Sets the time required to detect a communications error.
Adjustment may be needed when networking several drives.
Default: 2.0 s
Min.: 0.0
Max.: 10.0
618
H5-10
(0436)
Unit Selection for
MEMOBUS/Modbus
Register 0025H
CommReg 25h Unit
0: 0.1 V
1: 1 V
All Modes
0: 0.1 V units
1: 1 V units
Default: 0
Range: 0, 1
618
B.9 H Parameters: Multi-Function Terminals
546
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual