Table A.5 Power Ratings (Three-Phase 400 V Class) Continued
Item Specification
Drive Model
4o0096 4o0124 4o0156 4o0180 4o0216 4o0240 4o0302 4o0361 4o0414
Maximum Applicable Motor
Capacity kW (HP)
<1>
HD Rating 45 (60) 55 (75) 75 (100) 90 (125) 110 (150)
132 (175)
150 (200) 185 (250) 220 (300)
ND Rating 55 (75) 75 (100) 90 (125) 110 (150) 132 (175)
150 (200)
185 (250) 220 (300) 260 (350)
Input/
Output
Rating
Rated Input
Current (A)
<2>
HD Rating 70 87 113 142 164 197 218 275 329
ND Rating 87 113 142 164 197 218 275 329 377
Rated Input
Capacity (kVA)
<3>
HD Rating 64 80 103 130 150 180 200 251 300
ND Rating 80 103 130 150 180 200 251 300 344
Rated Output
Current (A)
<4> <5>
HD Rating 77 96 124 156 180 216 240 302 361
ND Rating 96 124 156 180 216 240 302 361 414
Overload Tolerance
HD Rating: 150% of rated output current for 60 s
ND Rating: 120% of rated output current for 60 s
(Derating may be required for applications that start and stop frequently)
Carrier Frequency
4 kHz
(User adjustable up
to 8 kHz. Derating
may be required.)
4 kHz
(User adjustable up
to 6 kHz. Derating
may be required.)
4 kHz
Maximum Output Voltage (V)
Proportional to input voltage
<6>
Maximum Output Frequency (Hz) 400 Hz (User-adjustable)
Power
Supply
Rated Voltage
Rated Frequency
Three-phase 4Aoooo and 4Poooo 380 to 500 Vac 50/60 Hz
Three-phase 4Eoooo and 4Woooo 380 to 480 Vac 50/60 Hz
Allowable Voltage Fluctuation -15 to 10%
Allowable Frequency Fluctuation ±3% (Frequency fluctuation rate: 1 Hz/100 ms or less)
Allowable Phase Power Supply
Voltage Unbalance
2% or less
Harmonic Current Distortion
<6>
5% or less (IEEE519 compliant)
Input Power Factor 0.98 or more (During rated operation)
<1> The motor capacity (HP) refers to an NEC 4-pole motor. The rated output current of the drive should be equal to or greater than the motor current.
Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring
connections, and power supply impedance.
<3> Rated input capacity is calculated with a power line voltage of 480 V × 1.1.
<4> The rated output current of the drive should be equal to or greater than the motor rated current.
<5> Carrier frequency is set to 4 kHz. Current derating is required to raise the carrier frequency.
<6> Commercial power mode results in near zero input harmonics. Existing power conditions and operation mode can affect input harmonics.
A.2 Power Ratings