u
E3-01 (Motor 2 Control Mode) Dependent Parameters
Table B.5 E3-01 (Motor 2 Control Mode) Dependent Parameters and Default Values
No. Name Setting Range Resolution
Control Modes (E3-01)
V/f (0) V/f w/PG (1) OLV (2) CLV (3)
C3-21 Motor 2 Slip Compensation Gain 0.0 to 2.5 0.1 0.0 1.0 1.0
C3-22
Motor 2 Slip Compensation Primary Delay
Time
0 to 10000 1 ms 2000 200
C5-21 Motor 2 ASR Proportional Gain 1 0.00 to 300.00 0.01 0.20 20.00
C5-22 Motor 2 ASR Integral Time 1 0.000 to 10.000 0.001 s 0.200 0.500
C5-23 Motor 2 Proportional Gain 2 0.00 to 300.00 0.01 0.02 20.00
C5-24 Motor 2 ASR Integral Time 2 0.000 to 10.000 0.001 s 0.050 0.500
C5-26 Motor 2 Carrier Frequency Selection 1 to 4; F
7
<1>
7
<1>
7
<1>
7
<1>
E3-04 Motor 2 Maximum Output Frequency 40.0 to 400.0 0.1 Hz 60.0 60.0 60.0 60.0
E3-05
Motor 2 Maximum Output Voltage
<2>
0.0 to 255.0 0.1 V 200.0 200.0 200.0 200.0
E3-06 Motor 2 Base Frequency 0.0 to 400.0 0.1 Hz 60.0 60.0 60.0 60.0
E3-07 Motor 2 Mid Output Frequency 0.0 to 400.0 0.1 Hz 3.0 3.0 3.0 0.0
E3-08
Motor 2 Mid Output Frequency Voltage
<2>
0.0 to 255.0 0.1 V 15.0 15.0 11.0 0.0
E3-09 Motor 2 Minimum Output Frequency 0.0 to 400.0 0.1 Hz 1.5 1.5 0.5 0.0
E3-10
Motor 2 Minimum Output Voltage
<2>
0.0 to 255.0 0.1 V 9.0 9.0 2.0 0.0
<1> Default setting is determined by parameters o2-04, Drive Model Selection, and C6-01, Drive Duty Selection.
<2> Values shown here are specific to 200 V class drives. Double the value for 400 V class drives.
B.16 Control Mode Dependent Parameter Default Values
586
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual