No. Name Setting Range Default
o4-05 Capacitor Maintenance Setting 0 to 150% 0%
n
o4-07: DC Bus Pre-Charge Relay Maintenance Setting
Sets the value of the softcharge bypass relay maintenance time displayed in U4-06 as a percentage of the total expected
performance life. Reset this value to 0 after replacing the bypass relay.
Note: The actual maintenance time will depend on the environment where the drive is used.
No. Name Setting Range Default
o4-07 DC Bus Pre-charge Relay Maintenance Setting 0 to 150% 0%
n
o4-11: U2, U3 Initialization
Resets the fault trace and fault history monitors (U2-oo and U3-oo).
Note: Initializing the drive using A1-03 does not reset these monitors.
No. Name Setting Range Default
o4-11 U2, U3 Initialization 0, 1 0
Setting 0: No Action
The drive keeps the previously saved record concerning fault trace and fault history.
Setting 1: Reset Fault Data
Resets the data for the U2-oo and U3-oo monitors. Setting o4-11 to 1 and pressing the ENTER key erases fault data and
returns the display to 0.
n
o4-12: kWh Monitor Initialization
Resets the electric power (U9-01 to U9-03) and regenerative power (U9-04 to U9-06). Resets electric power rate (U9-07 to
U9-10) and regenerative power rate (U9-11 to U9-14).
No. Name Setting Range Default
o4-12 kWh Monitor Initialization 0, 1 0
Setting 0: No Action
Setting 1: Reset kWh Data
n
o4-13: Number of Run Commands Counter Initialization
Resets the Run command counter displayed in U4-02. Initializing the drive or cycling the power does not reset this monitor.
No. Name Setting Range Default
o4-13 Number of Run Commands Counter Initialization 0, 1 0
Setting 0: No Action
The Run command data are kept.
Setting 1: Number of Run Commands Counter
Resets the Run command counter. The monitor U4-02 will show 0. Setting o4-13 to 1 and pressing the ENTER key erases the
counter value and returns the display to 0.
n
o4-19: Power Unit Price
Sets the price per 1 kWh to calculate the power rate displayed for total consumed power (U9-07 to U9-10) and total regenerated
power (U9-11 to U9-14).
No. Name Setting Range Default
o4-19 Power Unit Price 0.00 to 650.00 000.00
u
q: DriveWorksEZ Parameters
These parameters are reserved for use with DriveWorksEZ. Refer to the DriveWorksEZ manual for more information.