B.4 b: Application
Application parameters configure the source of the Run command, DC Injection Braking, Speed Search, timer functions, PID
control, the Dwell function, Energy Savings, and a variety of other application-related settings.
u
b1: Operation Mode Selection
No.
(Addr.
Hex)
Name LCD Display Description Values Page
b1-01
(0180)
Frequency Reference
Selection 1
Ref Source 1
0: Operator
1: Analog Input
2: Serial Com
3: Option PCB
4: Pulse Input
All Modes
0: Digital operator
1: Analog input terminals
2: MEMOBUS/Modbus communications
3: Option PCB
4: Pulse train input (terminal RP)
Default: 1
Range: 0 to 4
187
b1-02
(0181)
Run Command
Selection 1
Run Source 1
0: Operator
1: Digital Inputs
2: Communication
3: Option PCB
All Modes
0: Digital operator
1: Digital input terminals
2: MEMOBUS/Modbus communications
3: Option PCB
Default: 1
Range: 0 to 3
188
b1-03
(0182)
Stopping Method
Selection
Stopping Method
0: Ramp to Stop
1: Coast to Stop
2: DCInj to Stop
3: Coast w/Timer
All Modes
0: Ramp to stop
1: Coast to stop
2: DC Injection Braking to stop
3: Coast with timer
Default: 0
Range: 0 to 3
<1>
189
b1-04
(0183)
Reverse Operation
Selection
Reverse Oper
0: Reverse Enabled
1: Reverse Disabled
All Modes
0: Reverse enabled.
1: Reverse disabled.
Default: 0
Range: 0, 1
192
b1-05
(0184)
Action Selection below
Minimum Output
Frequency
Zero-Speed Oper
0: RUN at Freq Ref
1: STOP
2: RUN at Min Freq
RUN at Zero PRM
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
0: Operates according to frequency reference (E1-09 is
disabled).
1: Output shuts off (coast to stop if less than E1-09).
2: Operates according to E1-09 (frequency reference set to
E1-09).
3: Zero speed (frequency reference becomes zero when less than
E1-09).
Default: 0
Range: 0 to 3
192
b1-06
(0185)
Digital Input Reading
Cntl Input Scans
0: 1 Scan
1: 2 Scans
All Modes
0: Input status is read once and processed immediately (for
quicker response)
1: Input is read twice and processed only if the status is the same
in both readings (robust against noisy signals)
Default: 1
Range: 0, 1
193
b1-07
(0186)
LOCAL/REMOTE Run
Selection
LOC/REM Dur Run
0: Cycle Extrn RUN
1: Accept Extrn RUN
All Modes
0: An external Run command must be cycled at the new source
in order to be activated.
1: An external Run command at the new source is accepted
immediately.
Default: 0
Range: 0, 1
194
b1-08
(0187)
Run Command Selection
in Programming Mode
RUN dur PRG Mode
0: Run
Disabled@PRG
1: Run Enabled@PRG
2: Prg only @ Stop
All Modes
0: Run command is not accepted while in Programming Mode.
1: Run command is accepted while in Programming Mode.
2: Prohibit entering Programming Mode during run.
Default: 0
Range: 0 to 2
194
b1-14
(01C3)
Phase Order Selection
Rotation Sel
0: Standard
1: SwitchPhaseOrder
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
0: Standard
1: Switch phase order (reverses the direction of the motor)
Default: 0
Range: 0, 1
194
B.4 b: Application
494
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual