Three-Phase 400 V Class Drive Models 4o0011 to 4o0077
Table A.4 Power Ratings (Three-Phase 400 V Class)
Item Specification
Drive Model
4o0011 4o0014 4o0021 4o0027 4o0034 4o0040 4o0052 4o0065 4o0077
Maximum Applicable Motor
Capacity kW (HP)
<1>
HD Rating 3.7 (5) 5.5 (7.5) 7.5 (10) 11 (15) 15 (20) 18.5 (25) 22 (30) 30 (40) 37 (50)
ND Rating 5.5 (7.5) 7.5 (10) 11 (15) 15 (20) 18.5 (25) 22 (30) 30 (40) 37 (50) 45 (60)
Input/
Output
Rating
Rated Input
Current (A)
<2>
HD Rating 8.7 10 13 19 25 31 36 47 59
ND Rating 10 13 19 25 31 36 47 59 70
Rated Input
Capacity (kVA)
<3>
HD Rating 8 9 12 17 22 28 33 43 54
ND Rating 9 12 17 22 28 33 43 54 64
Rated Output
Current (A)
<4> <5>
HD Rating 9.6 11 14 21 27 34 40 52 65
ND Rating 11 14 21 27 34 40 52 65 77
Overload Tolerance
HD Rating: 150% of rated output current for 60 s
ND Rating: 120% of rated output current for 60 s
(Derating may be required for applications that start and stop frequently)
Carrier Frequency 4 kHz (User adjustable up to 10 kHz. Derating may be required.)
Maximum Output Voltage (V)
Proportional to input voltage
<6>
Maximum Output Frequency (Hz) 400 Hz (User-adjustable)
Power
Supply
Rated Voltage
Rated Frequency
Three-phase 4Aoooo and 4Poooo 380 to 500 Vac 50/60 Hz
Three-phase 4Eoooo and 4Woooo 380 to 480 Vac 50/60 Hz
Allowable Voltage Fluctuation -15 to 10%
Allowable Frequency Fluctuation ±3% (Frequency fluctuation rate: 1 Hz/100 ms or less)
Allowable Phase Power Supply
Voltage Unbalance
2% or less
Harmonic Current Distortion
<6>
5% or less (IEEE519 compliant)
Input Power Factor 0.98 or more (During rated operation)
<1> The motor capacity (HP) refers to an NEC 4-pole motor. The rated output current of the drive should be equal to or greater than the motor current.
Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring
connections, and power supply impedance.
<3> Rated input capacity is calculated with a power line voltage of 480 V × 1.1.
<4> The rated output current of the drive should be equal to or greater than the motor rated current.
<5> Carrier frequency is set to 4 kHz. Current derating is required to raise the carrier frequency.
<6> Commercial power mode results in near zero input harmonics. Existing power conditions and operation mode can affect input harmonics.