B.3 A: Initialization Parameters
The A parameter group creates the operating environment for the drive. This includes the parameter Access Level, Motor
Control Method, Password, User Parameters and more.
u
A1: Initialization
No.
(Addr.
Hex)
Name LCD Display Description Values Page
A1-00
(0100)
<1>
Language Selection
Select Language
0: English
1: (Japanese)
2: Deutsch
3: Français
4: Italiano
5: Español
6: Portuguêse
7:
All Modes
0: English
1: Japanese
2: German
3: French
4: Italian
5: Spanish
6: Portuguese
7: Chinese
Default: 0
Range: 0 to 7
180
A1-01
(0101)
<2>
Access Level Selection
Access Level
0: Operation Only
1: User Parameters
2: Advanced Level
All Modes
0: View and set A1-01 and A1-04. Uo-oo parameters can also
be viewed.
1: User Parameters (access to a set of parameters selected by the
user, A2-01 to A2-32)
2: Advanced Access (access to view and set all parameters)
Default: 2
Range: 0 to 2
180
A1-02
(0102)
<1>
Control Method
Selection
Control Method
0: V/f Control
1: V/f with PG
2: Open Loop Vector
3: Closed Loop Vect
5: PM OpenLoop Vect
6: PM
AdvOpLoopVect
7: PM ClosedLoopVct
All Modes
0: V/f Control
1: V/f Control with PG
2: Open Loop Vector Control
3: Closed Loop Vector Control
5: Open Loop Vector Control for PM
6: Advanced Open Loop Vector Control for PM
7: Closed Loop Vector Control for PM
Default: 0
Range: 0 to 3;
5 to7
180
A1-03
(0103)
Initialize Parameters
Init Parameters
0: No Initialize
1110: User Initialize
2220: 2-Wire Initial
3330: 3-Wire Initial
5550: Term->Cntrl Int
All Modes
0: No initialization
1110: User Initialize (parameter values must be stored using
parameter o2-03)
2220: 2-Wire initialization
3330: 3-Wire initialization
5550: oPE04 error reset
Default: 0
Range: 0 to
3330;
5550
181
A1-04
(0104)
Password Enter Password
All Modes
When the value set into A1-04 does not match the value set into
A1-05, parameters A1-01 through A1-03, A1-06, A1-07, and
A2-01 through A2-32 cannot be changed.
Default: 0000
Min.: 0000
Max.: 9999
182
A1-05
(0105)
Password Setting Select Password
All Modes
When the value set into A1-04 does not match the value set into
A1-05, parameters A1-01 through A1-03, A1-06, A1-07, and
A2-01 through A2-32 cannot be changed.
Default: 0000
Min.: 0000
Max.: 9999
182
A1-06
(0127)
Application Preset
Application Sel
0: General
1: Pump
2: Conveyor
3: Exhaust Fan
4: Supply Fan
5: Compressor
All Modes
0: General-purpose
1: Water supply pump
2: Conveyor
3: Exhaust fan
4: HVAC fan
5: Air compressor
Default: 0
Range: 0 to 5
184
A1-07
(0128)
DriveWorksEZ
Function Selection
DWEZ Func Sel
0: Disabled
1: Enabled
2: Terminal Control
All Modes
0: DWEZ Disabled
1: DWEZ Enabled
2: Digital input (enabled when H1-oo = 9F)
Default: 0
Range: 0 to 2
186
<1> Parameter setting value is not reset to the default value when the drive is initialized.
<2> Default setting value is determined by he Application Preset selected in parameter A1-06.
B.3 A: Initialization Parameters