YASKAWA U1000 - E4: Motor 2 Parameters

YASKAWA U1000
706 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Output (V)
Frequency (Hz)
E3-05
E3-12
E3-13
E3-08
E3-10
E3-09
E3-07
E3-06
E3-11
E3-04
Figure 5.54 V/f Pattern for Motor 2
Note: 1. The following conditions must be true when setting up the V/f pattern: E3-09 ≤ E3-07 < E3-06 ≤ Ε3-11 ≤ E3-04
2. To make the V/f pattern a straight line at a frequency lower than E3-06, set E3-09 equal to E3-07. In this case, E3-08 is disregarded.
3. Parameters E3-04 through E3-13 are reset to their default values when the drive is initialized.
4. Only use E3-11, E3-12, and E3-13 to fine-tune the V/f pattern in the constant output range. These parameters rarely need to be changed.
u
E4: Motor 2 Parameters
E4 parameters contain the motor data for motor 2. These parameters are usually set automatically during the Auto-Tuning
process for vector control modes (Rotational Auto-Tuning, Stationary Auto-Tuning 2, 3). Refer to Auto-Tuning Fault
Detection on page 397 for details if Auto-Tuning cannot be performed.
Note:
The function for switching between two motors cannot be used with a PM motor. E4-oo parameters are hidden when a PM motor control
mode is selected (A1-02 = 5, 6, or 7).
n
E4-01: Motor 2 Rated Current
Protects the motor and calculates torque limits. Set E4-01 to the full load amps (FLA) stamped on the nameplate of motor 2.
If Auto-Tuning completes successfully, the value entered to T1-04 will automatically be saved to E4-01.
No. Parameter Name Setting Range Default
E4-01 Motor 2 Rated Current
10 to 150% of the drive rated
current.
<1>
Determined by
C6-01 and o2-04
<1> Display is in the following units:
2o0028, 2o0042, and 4o0011 to 4o0027: 0.01 A units
2o0054 to 2o0248 and 4o0034 to 4o0930: 0.1 A units
Note: An oPE02 error will occur if the motor rated current in E4-01 is set lower than the motor no-load current in E4-03. Set E4-03 correctly to
prevent this error.
n
E4-02: Motor 2 Rated Slip
Sets the motor 2 rated slip frequency and is the basis for slip compensation value. The drive calculates this value automatically
during Auto-Tuning (Rotational Auto-Tuning and Stationary Auto-Tuning 2, 3).
Refer to E2-02: Motor Rated Slip on page 255 for information on calculating the motor rated slip.
No. Parameter Name Setting Range Default
E4-02 Motor 2 Rated Slip 0.00 to 20.00 Hz
Determined by
C6-01 and o2-04
n
E4-03: Motor 2 Rated No-Load Current
Sets the no-load current for motor 2 in amperes when operating at the rated frequency and the no-load voltage. The drive sets
E2-03 during the Auto-Tuning process (Rotational Auto-Tuning and Stationary Auto-Tuning 2, 3). The motor no-load current
listed in the motor test report can also be entered to E2-03 manually. Contact the motor manufacturer for a copy of the motor
test report.
No. Parameter Name Setting Range Default
E4-03 Motor 2 Rated No-Load Current
0 to [E4-01]
<1>
Determined by
C6-01 and o2-04
<1> Display is in the following units:
2o0028, 2o0042, and 4o0011 to 4o0027: 0.01 A units
2o0054 to 2o0248 and 4o0034 to 4o0930: 0.1 A units
5.5 E: Motor Parameters
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
259
5
Parameter Details