EasyManua.ls Logo

YASKAWA U1000 - H3: Multi-Function Analog Inputs

YASKAWA U1000
706 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
u
H3: Multi-Function Analog Inputs
No.
(Addr.
Hex)
Name LCD Display Description Values Page
H3-01
(0410)
Terminal A1 Signal
Level Selection
Term A1 Level
0: 0-10V,
(LowLim=0)
1: 0-10V, (BipolRef)
All Modes
0: 0 to 10 V
1: -10 to 10 V
Default: 0
Range: 0, 1
298
H3-02
(0434)
Terminal A1 Function
Selection
Term A1 FuncSel
All Modes
Sets the function of terminal A1.
Default: 0
Range: 0 to 32
298
H3-03
(0411)
Terminal A1 Gain
Setting
Terminal A1 Gain
All Modes
Sets the level of the input value selected in H3-02 when 10 V
is input at terminal A1.
Default: 100.0%
Min.: -999.9
Max.: 999.9
298
H3-04
(0412)
Terminal A1 Bias
Setting
Terminal A1 Bias
All Modes
Sets the level of the input value selected in H3-02 when 0 V is
input at terminal A1.
Default: 0.0%
Min.: -999.9
Max.: 999.9
298
H3-05
(0413)
Terminal A3 Signal
Level Selection
Term A3 Signal
0: 0-10V (LowLim=0)
1: 0-10V, (BipolRef)
All Modes
0: 0 to 10 V
1: -10 to 10 V
Default: 0
Range: 0, 1
299
H3-06
(0414)
Terminal A3 Function
Selection
Terminal A3 Sel
All Modes
Sets the function of terminal A3.
Default: 2
Range: 0 to 32
299
H3-07
(0415)
Terminal A3 Gain
Setting
Terminal A3 Gain
All Modes
Sets the level of the input value selected in H3-06 when 10 V
is input at terminal A3.
Default: 100.0%
Min.: -999.9
Max.: 999.9
300
H3-08
(0416)
Terminal A3 Bias
Setting
Terminal A3 Bias
All Modes
Sets the level of the input value selected in H3-06 when 0 V is
input at terminal A3.
Default: 0.0%
Min.: -999.9
Max.: 999.9
300
H3-09
(0417)
Terminal A2 Signal
Level Selection
Term A2 Level
All Modes
0: 0 to 10 V
1: -10 to 10 V
2: 4 to 20 mA
3: 0 to 20 mA
Note: Use DIP switch S1 to set input terminal A2 for a
current or a voltage input signal.
Default: 2
Range: 0 to 3
300
H3-10
(0418)
Terminal A2 Function
Selection
Term A2 FuncSel
All Modes
Sets the function of terminal A2.
Default: 0
Range: 0 to 32
300
H3-11
(0419)
Terminal A2 Gain
Setting
Terminal A2 Gain
All Modes
Sets the level of the input value selected in H3-10 when 10 V
(20 mA) is input at terminal A2.
Default: 100.0%
Min.: -999.9
Max.: 999.9
300
H3-12
(041A)
Terminal A2 Bias
Setting
Terminal A2 Bias
All Modes
Sets the level of the input value selected in H3-10 when 0 V (0
or 4 mA) is input at terminal A2.
Default: 0.0%
Min.: -999.9
Max.: 999.9
300
H3-13
(041B)
Analog Input Filter
Time Constant
A1/A2 Filter T
All Modes
Sets a primary delay filter time constant for terminals A1, A2,
and A3. Used for noise filtering.
Default: 0.03 s
Min.: 0.00
Max.: 2.00
300
H3-14
(041C)
Analog Input Terminal
Enable Selection
A1/A2/A3 Sel
1: A1 Available
2: A2 Available
3: A1/A2 Available
4: A3 Available
5: A1/A3 Available
6: A2/A3 Available
7: All Available
All Modes
Determines which analog input terminals will be enabled or
disabled when a digital input programmed for “Analog input
enable” (H1-oo = C) is activated.
The terminals not set as the target are not influenced by input
signals.
1: Terminal A1 only
2: Terminal A2 only
3: Terminals A1 and A2 only
4: Terminal A3 only
5: Terminals A1 and A3
6: Terminals A2 and A3
7: All terminals enabled
Default: 7
Range: 1 to 7
301