n
H3-14: Analog Input Terminal Enable Selection
When one of the multi-function digital input parameters is set for “Analog input enable” (H1-oo = C), the value set to H3-14
determines which analog input terminals are enabled when the input is closed. All of the analog input terminals will be enabled
all of the time when H1-oo≠ C. The terminals not set as the target are not influenced by input signals.
No. Name Setting Range Default
H3-14 Analog Input Terminal Enable Selection 1 to 7 7
Setting 1: A1 Only Enabled
Setting 2: A2 Only Enabled
Setting 3: A1 and A2 Only Enabled
Setting 4: A3 Only Enabled
Setting 5: A1 and A3 Only Enabled
Setting 6: A2 and A3 Only Enabled
Setting 7: All Analog Input Terminals Enabled
n
H3-16 to H3-18: Terminal A1/A2/A3 Offset
Set the offset level of the selected input value to terminals A1, A2, or A3 that is equal to 0 Vdc input. These parameters rarely
require adjustment.
No. Name Setting Range Default
H3-16 Terminal A1 Offset -500 to 500 0
H3-17 Terminal A2 Offset -500 to 500 0
H3-18 Terminal A3 Offset -500 to 500 0
n
Multi-Function Analog Input Terminal Settings
See Table 5.42 for information on how H3-02, H3-10, and H3-06 determine functions for terminals A1, A2, and A3.
Note: The scaling of all input functions depends on the gain and bias settings for the analog inputs. Set these to appropriate values when selecting
and adjusting analog input functions.
Table 5.42 Multi-Function Analog Input Terminal Settings
Setting Function Page
0 Frequency Bias 301
1 Frequency Gain 302
2 Auxiliary Frequency Reference 1 302
3 Auxiliary Frequency Reference 2 302
4 Output Voltage Bias 302
5 Accel/Decel Time Gain 302
6 DC Injection Braking Current 302
7 Torque Detection Level 302
8 Stall Prevention Level During Run 302
9 Output Frequency Lower Limit Level 303
B PID Feedback 303
C PID Setpoint 303
D Frequency Bias 303
Setting Function Page
E Motor Temperature (PTC Input) 303
F Through Mode 303
10 Forward Torque Limit
30311 Reverse Torque Limit
12 Regenerative Torque limit
13 Torque Limit Using Torque Reference/Speed Limit 303
14 Torque Compensation 303
15 General Torque Limit 303
16 Differential PID Feedback 303
1F Through Mode 303
30 DriveWorksEZ Analog Input 1
30331 DriveWorksEZ Analog Input 2
32 DriveWorksEZ Analog Input 3
Setting 0: Frequency Bias
The input value of an analog input set to this function will be added to the analog frequency reference value. When the frequency
reference is supplied by a different source other than the analog inputs, this function will have no effect. Use this setting also
when only one of the analog inputs is used to supply the frequency reference.
By default, analog inputs A1 and A2 are set for this function. Simultaneously using A1 and A2 increases the frequency reference
by the total of all inputs.
5.7 H: Terminal Functions
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
301
5
Parameter Details