No.
(Addr.
Hex)
Name LCD Display Description
Analog
Output Level
Unit
U2-54
(0843)
Power Supply Voltage at
Previous Fault
PowerSupply Volt
All Modes
Displays the power supply voltage at the previous fault.
Displayed as in U1-54.
No signal output
available
1 V
U2-58
(0847)
Power Supply
Frequency at Previous
Fault
PowerSupply Freq
All Modes
Displays the power supply frequency at the previous fault.
Displayed as in U1-58.
No signal output
available
0.1 Hz
<1> Display is in the following units:
2o0028, 2o0042, and 4o0011 to 4o0027: 0.01 A units
2o0054 to 2o0248 and 4o0034 to 4o0720: 0.1 A units
4o0900 and 4o0930: 1 A units
<2> The values of U1-03, U2-05, and U4-13 are displayed on the digital operator in units of amperes. When those monitors are checked using
MEMOBUS/Modbus communications, the monitor values in MEMOBUS/Modbus communications are displayed as: numeric value / 8192 × drive
rated current (A) from the condition “192 (maximum value) = drive rated current (A)”
Note: Note: Fault histories are not kept when CPF00, CPF01, CPF06, CPF24, oFA00, oFb00, oFC00, Uv1, Uv2, or Uv3 occur.
u
U3: Fault History
No.
(Addr.
Hex)
Name LCD Display Description
Analog
Output Level
Unit
U3-01 to
U3-04
(0090 to
0093
(0800 to
0803))
1st to 4th Most Recent
Fault
Fault Message o
All Modes
Displays the first to the fourth most recent faults.
No signal output
available
U3-05 to
U3-10
(0804 to
0809)
5th to 10th Most Recent
Fault
Fault Message o
All Modes
Displays the fifth to the tenth most recent faults.
After ten faults, data for the oldest fault is deleted. The most
recent fault appears in U3-01, with the next most recent fault
appearing in U3-02. The data is moved to the next monitor
parameter each time a fault occurs.
No signal output
available
U3-11 to
U3-14
(0094 to
0097
(080A to
080D))
Cumulative Operation
Time at 1st to 4th Most
Recent Fault
Elapsed Time o
All Modes
Displays the cumulative operation time when the first to the
fourth most recent faults occurred.
No signal output
available
1 h
U3-15 to
U3-20
(080E to
0813)
Cumulative Operation
Time at 5th to 10th Most
Recent Fault
Elapsed Time o
All Modes
Displays the cumulative operation time when the fifth to the tenth
most recent faults occurred.
No signal output
available
1 h
Note: Note: Fault histories are not kept when CPF00, CPF01, CPF06, CPF24, oFA00, oFb00, oFC00, Uv1, Uv2, or Uv3 occur.