Table 4.16 Auto-Tuning Input Data
Input Value
Input
Parameter
Unit
Tuning Type (T1-01)
0
Standard
2
Line-to-Line
Resistance
3
Rotational for V/
f Control
4
Stationary 2
5
Stationary 3
Control Mode A1-02 – 2, 3 0, 1, 2, 3 0, 1 2, 3 2, 3
Motor Rated Power T1-02 kW YES YES YES YES YES
Motor Rated Voltage T1-03 Vac YES – YES YES YES
Motor Rated Current T1-04 A YES YES YES YES YES
Motor Rated Frequency T1-05 Hz YES – YES YES YES
Number of Motor Poles T1-06 - YES – YES YES YES
Motor Rated Speed T1-07 r/min YES – YES YES YES
PG Number of Pulses per
Revolution
T1-08 -
YES
<1>
– –
YES
<1>
YES
<1>
Motor No-Load Current T1-09 A – – – YES YES
Motor Rated Slip T1-10 Hz – – – YES YES
Motor Iron Loss T1-11 W – – YES – YES
<1> Input data is needed for CLV/PM only.
n
Auto-Tuning for Permanent Magnet Motors
Automatically sets the V/f pattern and motor parameters E1-oo and E5-oo when a PM motor is used. Additionally, the
feature also sets some F1-oo parameters for speed feedback detection in Closed Loop Vector.
Table 4.17 Types of Auto-Tuning for Permanent Magnet Motors
Type Setting Application Conditions and Benefits
Control Mode
OLV/PM AOLV/PM CLV/PM
PM Motor Parameter
Settings
T2-01 = 0
• Motor does not rotate during Auto-Tuning.
• Motor data similar to Table 4.18 are available from test
report or motor nameplate.
YES YES YES
PM Stationary Auto-
Tuning
T2-01 = 1
• A motor test report listing motor data is not available.
• Drive automatically calculates and sets motor parameters.
YES YES YES
PM Stationary Auto-
Tuning for Stator
Resistance
T2-01 = 2
• Useful to tune the drive when the motor data were set up
manually or by motor code and the cable is longer than 50
m.
• Should also be performed if the cable length has changed
after prior tuning.
YES YES YES
Z Pulse Offset Tuning T2-01 = 3
• PG encoder has been replaced. Calculates the Z Pulse
offset.
• Requires the motor to rotate with no load or very low load.
– – YES
Back EMF Constant
Tuning
T2-01 = 11
• Use when a motor test is not available.
• Tunes the motor induction voltage only.
• Should be performed after motor data are set and the
encoder offset is adjusted.
• The motor must be uncoupled from the mechanical system
(remove loads).
– – YES
High Frequency
Injection Parameter
Tuning
T2-01 = 13
• The motor rotated in reverse or STo fault (Motor Step-Out)
occurred at startup in OLV/PM.
• Low speed and insufficient or no torque after activating the
high frequency injection control (n8-57 = 1) in AOLV/
PM.
• Faults, such as the motor rotating in reverse, occurred when
the power was turned on during initial startup in CLV/PM.
– YES YES
PM Rotational Auto-
Tuning
T2-01 = 14
• A motor test report listing motor data is not available.
• Motor can be decoupled from the load and rotate freely
while Auto-Tuning is performed. Drive automatically
calculates and sets motor parameters.
• PM Rotational Auto-Tuning gives more accurate results
than Stationary Auto-Tuning.
YES YES YES
4.7 Auto-Tuning
158