Table 5.33 High Starting Torque, Settings 8 to B
Setting = 8 50 Hz Setting = 9 50 Hz Setting = A 60 Hz Setting = B 60 Hz
0
7
200
1.3 2.5 50
15
Voltage (V)
Frequency (Hz)
0
9
200
1.3 2.5 50
20
Voltage (V)
Frequency (Hz)
0
7
200
1.5 3 60
15
Voltage (V)
Frequency (Hz)
0
11
200
1.5 3 60
20
Voltage (V)
Frequency (Hz)
Table 5.34 Constant Output, Settings C to F
Setting = C 90 Hz Setting = D 120 Hz Setting = E 180 Hz Setting = F 60 Hz
0
6
12
200
1.5 3 9060
Voltage (V)
Frequency (Hz)
0
6
12
200
1.5 3 12060
Voltage (V)
Frequency (Hz)
0
6
12
200
1.5 3 18060
Voltage (V)
Frequency (Hz)
0
6.9
230
1.5 3 60
13.8
Voltage (V)
Frequency (Hz)
Setting a Custom V/f Pattern (Setting F: Default)
Setting parameter E1-03 to F allows the user to set up a custom V/f pattern by changing parameters E1-04 to E1-13.
n
V/f Pattern Settings E1-04 to E1-13
If E1-03 is set to a preset V/f pattern (i.e., a value other than F), the user can monitor the V/f pattern in parameters E1-04
through E1-13. To create a new V/f pattern, set E1-03 to F. Refer to V/f Pattern on page 255 for an example custom V/f
pattern.
Note:
Certain E1-oo parameters might not be visible depending on the control mode. Refer to Parameter List on page 489 for details.
No. Parameter Name Setting Range Default
E1-04 Maximum Output Frequency
40.0 to 400.0 Hz
<1> <2> <3>
E1-05 Maximum Voltage
0.0 to 255.0 V
<4> <2>
E1-06 Base Frequency 0.0 to [E1-04]
<2> <3>
E1-07 Middle Output Frequency 0.0 to [E1-04]
<2>
E1-08 Middle Output Frequency Voltage
0.0 to 255.0 V
<4> <2>
E1-09 Minimum Output Frequency
0.0 to [E1-04]
<1> <2> <3>
E1-10 Minimum Output Frequency Voltage
0.0 to 255.0 V
<4> <2>
E1-11 Middle Output Frequency 2 0.0 to [E1-04]
0.0 Hz
<6>
E1-12 Middle Output Frequency Voltage 2
0.0 to 255.0 V
<4>
0.0 V
<5>
<6>
E1-13 Base Voltage
0.0 to 255.0 V
<4>
0.0 V
<5>
<7>
<1> Default setting is determined by E5-01 in OLV/PM. When E5-01 is set to FFFFH, the setting range for E1-04 and E1-06 is 10.0 to 40.0 Hz and the
setting range for E1-09 is 0.0 to 400.0 Hz.
<2> Default setting is determined by the control mode.
<3> When using PM motors, the default setting is determined by the motor code set to E5-01.
<4> Values shown are specific to 200 V class drives. Double the value for 400 V class drives.
<5> The drive changes these settings when Auto-Tuning is performed (Rotational Auto-Tuning, Stationary Auto-Tuning 1, 2).
<6> Parameter ignored when E1-11 and E1-12 are set to 0.0.
<7> E1-13 and E1-05 are set to the same value when Auto-Tuning is performed.
5.5 E: Motor Parameters
254