No.
(Addr.
Hex)
Name LCD Display Description Values Page
F1-32
(03B1)
PG 2 Rotation Selection
PG2 Rotation Sel
0: Fwd = C.C.W
1: Fwd = C.W.
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLVV/f w PG CLVV/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLVV/f w PG CLV
0: Pulse A leads
1: Pulse B leads
Default: 0
Range: 0, 1
265
F1-33
(03B2)
PG 2 Gear Teeth 1 PG2 Gear Teeth1
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLVV/f w PG
Sets the gear ratio between the motor shaft and the encoder
(PG).
A gear ratio of 1 will be used if F1-33 or F1-34 are set to 0.
Default: 0
Min.: 0
Max.: 1000
265
F1-34
(03B3)
PG 2 Gear Teeth 2 PG2 Gear Teeth2
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLVV/f w PG
Sets the gear ratio between the motor shaft and the encoder
(PG). A gear ratio of 1 will be used if F1-33 or F1-34 are set to
0.
Default: 0
Min.: 0
Max.: 1000
265
F1-35
(03BE)
PG 2 Division Rate for
Pulse Monitor
PG2 Output Ratio
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLVV/f w PG CLVV/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLVV/f w PG CLV
Sets the division ratio for the pulse monitor used of the PG
option card 2 installed to port CN5-B.
When setting for a three-digit number “xyz”, the division ratio
becomes = [(1 + x) / yz].
Default: 1
Min.: 1
Max.: 132
265
F1-36
(03B5)
PG Option Card
Disconnect Detection 2
PGCardDisconDet1
0: Disabled
1: Enabled
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLVV/f w PG CLVV/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLVV/f w PG CLV
0: Disabled
1: Enabled
Default: 1
Range: 0, 1
266
F1-37
(03BD)
PG 2 Signal Selection
PG2 Signal Sel
0: A Phase Det
1: A,B Phase Det
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLVV/f w PG
0: A pulse detection
1: AB pulse detection
Default: 0
Range: 0, 1
266
F1-50
(03D2)
Encoder Selection
Encoder Select
0: EnDat Sin/Cos
1: EnDat SerialOnly
2: Hiperface
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
CLV/PM
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
CLV/PM
Selects the encoder connected the PG-F3 option.
0: EnDat 2.1/01, 2.2/01 Serial Communication + Sin/Cos
1: EnDat 2.2/22 Serial Communication
2: Hiperface
Note: The use of EnDat2.2/22 encoders requires a PG-
F3 option with software version 0102 or later. To
identify the PG-F3 software version refer to the
PG-F3 label in the field designated “C/N” (S +
four digit number).
Default: 0
Range: 0 to 2
267
F1-51
(03D3)
PGoH Detection Level PGOH Det Level
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
CLV/PM
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
CLV/PM
Sets the level for detecting PG Hardware Fault (PGoH).
Available when F1-20 = 1
Default: 80%
Min.: 1
Max.: 100
267
F1-52
(03D4)
Communication Speed
of Serial Encoder
Selection
Ser Enc Comm Spd
0: 1M/9600bps
1: 500k/19200bps
2: 1M/38400bps
3: 1M/38400bps
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
CLV/PM
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
CLV/PM
Selects the communication speed between the PG-F3 option
and serial encoder.
0: 1M bps/9600 bps (EnDat 2.2/22 / Hiperface)
1: 500k bps/19200 bps (EnDat 2.2/22 / Hiperface)
2: 1M bps/38400 bps (EnDat 2.2/22 / Hiperface)
3: 1M bps/38400 bps (EnDat 2.2/22 / Hiperface)
Default: 0
Range: 0 to 3
267
<1> Default setting is determined by parameter A1-02, Control Method Selection.