No.
(Addr.
Hex)
Name LCD Display Description Values Page
F7-14
(03F2)
Duplex Mode Selection
Duplex Select
0: Half/Half
1: Auto/Auto
2: Full/Full
3: Half/Auto
4: Half/Full
5: Auto/Half
6: Auto/Full
7: Full/Half
8: Full/Auto
All Modes
Selects duplex mode setting.
0: Half duplex forced
1: Auto-negotiate duplex mode and communication speed
2: Full duplex forced
3: Half duplex forced (port 1)/Auto-negotiate duplex mode and
communication speed (port 2)
4: Half duplex forced (port 1)/Full duplex forced (port 2)
5: Auto-negotiate duplex mode and communication speed
(port 1)/Half duplex forced (port 2)
6: Auto-negotiate duplex mode and communication speed
(port 1)/Full duplex forced (port 2)
7: Full duplex forced (port 1)/Half duplex forced (port 2)
8: Full duplex forced (port 1)/Auto-negotiate duplex mode and
communication speed (port 2)
Default: 1
Range: 0 to 8
F7-15
(03F3)
Communication Speed
Selection
Baud Rate
10: 10/10 Mbps
100: 100/100 Mbps
101: 10/100 Mbps
102: 100/10 Mbps
All Modes
Sets the communication speed
10: 10 Mbps
100: 100 Mbps
101: 10 Mbps (port 1)/100 Mbps (port 2)
102: 100 Mbps (port 1)/10 Mbps (port 2)
Default: 10
Range: 10 to 102
F7-16
(03F4)
Communication Loss
Time Out
CommLoss Tout
All Modes
Sets the time out value for communication loss detection in
tenths of a second. A value of 0 disables the connection time
out.
Example: An entered value of 100 represents 10.0 seconds.
Default: 0.0 s
Min.: 0.0
Max.: 30.0
F7-17
(03F5)
EtherNet/IP Speed
Scaling Factor
EN Speed Scale
All Modes
Sets the scaling factor for the speed monitor in EtherNet/IP
Class ID 2AH Object.
Default: 0
Min.: -15
Max.: 15
F7-18
(03F6)
EtherNet/IP Current
Scaling Factor
EN Current Scale
All Modes
Sets the scaling factor for the output current monitor in
EtherNet/IP Class ID 2AH Object.
Default: 0
Min.: -15
Max.: 15
F7-19
(03F7)
EtherNet/IP Torque
Scaling Factor
EN Torque Scale
All Modes
Sets the scaling factor for the torque monitor in EtherNet/IP
Class ID 2AH Object.
Default: 0
Min.: -15
Max.: 15
F7-20
(03F8)
EtherNet/IP Power
Scaling Factor
EN Power Scale
All Modes
Sets the scaling factor for the power monitor in EtherNet/IP
Class ID 2AH Object.
Default: 0
Min.: -15
Max.: 15
F7-21
(03F9)
EtherNet/IP Voltage
Scaling Factor
EN Voltage Scale
All Modes
Sets the scaling factor for the voltage monitor in EtherNet/IP
Class ID 2AH Object.
Default: 0
Min.: -15
Max.: 15
F7-22
(03FA)
EtherNet/IP Time
Scaling
EN Time Scale
All Modes
Sets the scaling factor for the time monitor in EtherNet/IP Class
ID 2AH Object.
Default: 0
Min.: -15
Max.: 15
F7-23 to
F7-27
(03FB to
03FF)
F7-28 to
F7-32
(0370 to
0374)
Dynamic Output
Assembly Parameters
All Modes
Parameters used in Output Assembly 116. Each parameter
contains a MEMOBUS/Modbus address. The value received
for Output Assembly 116 will be written to this corresponding
MEMOBUS/Modbus address. A MEMOBUS/Modbus
address value of 0 means that the value received for Output
Assembly 116 will not be written to any MEMOBUS/Modbus
register.
Default: 0
F7-33 to
F7-42
(0375 to
037E)
Dynamic Input
Assembly Parameters
All Modes
Parameters used in Input Assembly 166. Each parameter
contains a MEMOBUS/Modbus address. The value sent for
Input Assembly 166 will be read from this corresponding
MEMOBUS/Modbus address. A MEMOBUS/Modbus
address value of 0 means that the value sent for Input Assembly
166 is not defined by the user, therefore the option default
register value will be returned.
Default: 0
B.8 F: Option Settings
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
531