EasyManua.ls Logo

YASKAWA U1000 - Page 536

YASKAWA U1000
706 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
H1 Multi-Function Digital Input Selections
H1-oo
Setting
Function LCD Display Description Page
11 Down command Down Command 1
All Modes
The drive accelerates when the Up command terminal closes, and decelerates when
the Down command closes. When both terminals are closed or both are open, the
drive holds the frequency reference. The Up and Down commands must always
be used in conjunction with one another.
280
12 Forward Jog Forward Jog
All Modes
Closed: Runs forward at the Jog frequency d1-17.
281
13 Reverse Jog Reverse Jog
All Modes
Closed: Runs reverse at the Jog frequency d1-17.
281
14 Fault reset Fault Reset
All Modes
Closed: Resets faults if the cause is cleared and the Run command is removed.
281
15 Fast Stop (N.O.) Fast-Stop N.O.
All Modes
Closed: Decelerates at the Fast Stop time set to C1-09.
281
16 Motor 2 selection Motor 2 Select
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLVV/f V/f w PG OLV CLVV/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLVV/f V/f w PG OLV CLV
Open: Motor 1 (E1-oo, E2-oo)
Closed: Motor 2 (E3-oo, E4-oo)
282
17 Fast Stop (N.C.) Fast-Stop N.C.
All Modes
Open: Decelerates to stop at the Fast Stop time set to C1-09.
281
18 Timer function input Timer function
All Modes
Triggers the timer set up by parameters b4-01 and b4-02. Must be set in conjunction
with the timer function output (H2-oo = 12).
282
19 PID disable PID Disable
All Modes
Open: PID control enabled
Closed: PID control disabled
283
1A
Accel/decel time
selection 2
Multi-Acc/Dec 2
All Modes
Used in conjunction with an input terminal set for “Accel/decel time selection 1”
(H1-oo = 7), and allows the drive to switch between accel/decel times 3 and 4.
283
1B Program lockout Program Lockout
All Modes
Open: Parameters cannot be edited (except for U1-01 if the reference source is
assigned to the digital operator).
Closed: Parameters can be edited and saved.
283
1E Reference sample hold Ref Sample Hold
All Modes
Closed: Samples the analog frequency reference and operates the drive at that
speed.
283
B.9 H Parameters: Multi-Function Terminals
536
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual

Table of Contents

Other manuals for YASKAWA U1000