1-32
Pioneer Gold 3.00 Controller Technical Guide
BACnet
®
Legacy Analog Values
BACnet
®
Point #
Default
Limit
Range
BACnet
®
Point Name
BACnet
®
Description Unit
AV: 32 Space Heating Hi Reset
supply reset control in Heating Mode
Fahrenheit
AV: 33 Space Heating Lo Reset
supply reset control in Heating Mode
Fahrenheit
AV: 34 Supply Heating Hi Reset
supply reset control in Heating Mode
Fahrenheit
AV: 35 Supply Heating Lo Reset
supply reset control in Heating Mode
Fahrenheit
AV: 36 Dehum Enable Setpoint
Mode
Relative
Humidity
AV: 37 Degrees Fahrenheit that the supply air must be under
setpoint for auxiliary heat to enable
Fahrenheit
AV: 38 Supply Fan Max Percentage Maximum allowed output for a variable speed supply fan Percent
AV: 39 Supply Fan Minimum
Percentage
Minimum allowed output for a variable speed supply fan Percent
AV: 40 Fahrenheit
AV: 41 Fahrenheit
AV: 42 Fahrenheit
AV: 43 Leaving Water Temp Temperature of the loop water leaving the water coil Fahrenheit
AV: 44 Suction Temp Setpoint Not Used Fahrenheit
AV: 45
Percentage
Not Used Percent
AV: 46 Not Used Not Used GPM
AV: 47 Space Sensor Maximum
Maximum allowed user setpoint adjustment on the
Fahrenheit
AV: 48
Occupied cooling setpoint with the user adjustment from
Fahrenheit
AV: 49 Occupied Heating Setpoint with
Occupied heating setpoint with the user adjustment from
Fahrenheit
AV: 50 Water Valve Opening Delay
Time
compressor operation is allowed
Seconds
AV: 51 User Occupancy Override Time Minutes
AV: 52
Failure Time
going into compressor cooling.
Minutes
AV: 53 Waterside Econo Heating
Failure Time
going into compressor heating.
Minutes
AV: 54 Reheat Valve Percentage Position of modulating hot gas reheat valve Percent
AV: 55 Supply Reheat Setpoint Temperature setpoint of the discharge air while in
Fahrenheit
AV: 56 Space Temp Override
Fahrenheit
AV: 57 Space Humidity Override
Fahrenheit
AV: 58 This is an enumeration:
Table 1-16: BACnet
®
Legacy Analog Values (Continued)
BACnet
®
LEGACY PARAMETERS
BACnet
®
Legacy Analog Values