1-32
Pioneer Gold 3.00 Controller Technical Guide
BACnet
®
Legacy Analog Values
BACnet
®
Point #
Default
Limit
Range
BACnet
®
Point Name
BACnet
®
Description Unit
AV: 32   Space Heating Hi Reset 
supply reset control in Heating Mode
Fahrenheit
AV: 33   Space Heating Lo Reset 
supply reset control in Heating Mode
Fahrenheit
AV: 34   Supply Heating Hi Reset 
supply reset control in Heating Mode
Fahrenheit
AV: 35   Supply Heating Lo Reset 
supply reset control in Heating Mode
Fahrenheit
AV: 36   Dehum Enable Setpoint 
Mode
Relative
Humidity
AV: 37   Degrees Fahrenheit that the supply air must be under
setpoint for auxiliary heat to enable
Fahrenheit
AV: 38   Supply Fan Max Percentage Maximum allowed output for a variable speed supply fan Percent
AV: 39   Supply Fan Minimum
Percentage
Minimum allowed output for a variable speed supply fan Percent
AV: 40  󰀨 󰀨 Fahrenheit
AV: 41  󰀨 󰀨 Fahrenheit
AV: 42  󰀨 󰀨 Fahrenheit
AV: 43   Leaving Water Temp Temperature of the loop water leaving the water coil Fahrenheit
AV: 44   Suction Temp Setpoint Not Used Fahrenheit
AV: 45   
Percentage
Not Used Percent
AV: 46   Not Used Not Used GPM
AV: 47  Space Sensor Maximum
󰀨
Maximum allowed user setpoint adjustment on the

Fahrenheit
AV: 48   
󰀨
Occupied cooling setpoint with the user adjustment from

Fahrenheit
AV: 49   Occupied Heating Setpoint with
󰀨
Occupied heating setpoint with the user adjustment from

Fahrenheit
AV: 50   Water Valve Opening Delay
Time

compressor operation is allowed
Seconds
AV: 51   User Occupancy Override Time  Minutes
AV: 52   
Failure Time

going into compressor cooling.
Minutes
AV: 53   Waterside Econo Heating
Failure Time

going into compressor heating.
Minutes
AV: 54   Reheat Valve Percentage Position of modulating hot gas reheat valve Percent
AV: 55   Supply Reheat Setpoint Temperature setpoint of the discharge air while in

Fahrenheit
AV: 56   Space Temp Override 

Fahrenheit
AV: 57   Space Humidity Override 

Fahrenheit
AV: 58   This is an enumeration:
󰀨󰀨




Table 1-16: BACnet
®
Legacy Analog Values (Continued)
BACnet
®
LEGACY PARAMETERS
BACnet
®
Legacy Analog Values