1-42
Pioneer Gold 3.00 Controller Technical Guide
MODBUS Coil Points
Name Type
Function
Codes
Addr
Data
Type
Default
Value
Allowed
Range
Description
Network Occupy  

 Boolean False  
occupancy
Network Emergency
Shutdown
 

 Boolean False  
emergency shutdown
Dehum Priority  

 Boolean False  
other unit mode
Space/Supply
Cooling Reset
Enable
 

 Boolean False  
cooling mode
Space/Supply
Heating Reset
Enable
 

 Boolean False  
heating mode
Unit Lockout
Remote Reset
 

 Boolean False  
release a unit from an alarm lockout
Software Reset  

 Boolean False  
reset a control board
MODBUS Discrete Input Points
Name Type
Function
Codes
Addr
Data
Type
Description
Digital Input 1 Status Discrete Input   Boolean 
Occupancy Sensor Discrete Input   Boolean Status of occupancy sensor
Night Setback Enable Discrete Input   Boolean Status of the night setback enable input terminal
Night Setback Override Discrete Input   Boolean Status of the night setback override input terminal
Night Setback Tstat Discrete Input   Boolean Status of the night setback thermostat input terminal
Emergency Shutdown Status Discrete Input   Boolean Status of the emergency shutdown input terminal
Waterside Economizer Discrete Input   Boolean Status of the waterside economizer relay output
Compressor 1 Output Discrete Input   Boolean 
Compressor 1 2nd Step Discrete Input   Boolean 

Compressor 2 Output Discrete Input   Boolean 
compressors
Supply Fan Low Speed Discrete Input   Boolean Status of the low speed supply fan relay output
Supply Fan High Speed Discrete Input   Boolean Status of the high speed supply fan relay output
Electric Heat Discrete Input   Boolean Status of the electric heat relay output
Reversing Valve Discrete Input   Boolean Status of the reversing valve relay output
Water Valve/Pump Discrete Input   Boolean Status of the water valve or pump relay output
HGRH Discrete Input   Boolean Status of the hot gas reheat relay output
Alarm Discrete Input   Boolean Status of the alarm relay output and indicates if any
alarm is present
Table 1-20: MODBUS Coil Points
Table 1-21: MODBUS Discrete Input Points
MODBUS POINTS
MODBUS Coil and Discrete Input Points