1-37
Pioneer Gold 3.00 Controller Technical Guide
BACnet
®
MS/TP and IP Analog Values
BACnet
®
Point #
Default
Limit
Range
BACnet
®
Point Name
BACnet
®
Description
Unit
AV:1
Setpoint
setpoint to control the damper override output PPM
AV:2 Fahrenheit
AV:3 Fahrenheit
AV:4 Temperature setpoint of the discharge air while in cooling
mode
Fahrenheit
AV:5 Minimum on time setpoint for compressor(s) Seconds
AV:6 Seconds
AV:7
Delay
Interstage on delay setpoint when unit has more than one
compressor stage
Seconds
AV:8
Delay
compressor stage
Seconds
AV:9
Fahrenheit
AV:10
Fahrenheit
AV:11
Fahrenheit
AV:12
Fahrenheit
AV:13 Occupied Heating Setpoint Heating Mode Enable Setpoint when space is occupied Fahrenheit
AV:14 Unoccupied Heating Setpoint Heating Mode Enable Setpoint when space is unoccupied Fahrenheit
AV:15 Supply Heating Setpoint Temperature setpoint of the discharge air while in heating
mode
Fahrenheit
AV:16 Space Heating Hi Reset
supply reset control in Heating Mode
Fahrenheit
AV:17 Space Heating Lo Reset
supply reset control in Heating Mode
Fahrenheit
AV:18 Supply Heating Hi Reset
supply reset control in Heating Mode
Fahrenheit
AV:19 Supply Heating Lo Reset
supply reset control in Heating Mode
Fahrenheit
AV:20 Dehum Enable Setpoint
setpoint
Relative
Humidity
AV:21 Degrees Fahrenheit that the supply air must be under
Fahrenheit
AV:22 Supply Fan Maximum
Percentage
Maximum allowed output for a variable speed supply fan Percent
AV:23 Supply Fan Minimum
Percentage
Minimum allowed output for a variable speed supply fan Percent
AV:24 Fahrenheit
AV:25 Fahrenheit
AV:26 Fahrenheit
Table 1-16: BACnet
®
MS/TP and IP Parameter Analog Values
BACnet
®
MS/TP AND IP PARAMETERS
BACnet
®
MS/TP and IP Analog Values