Pioneer Gold 3.00 Controller Technical Guide
BACnet
®
MS/TP and IP Analog Values
BACnet
®
Point #
Default
Limit
Range
BACnet
®
Point Name
BACnet
®
Description
Unit
AV:1   
Setpoint 
setpoint to control the damper override output PPM
AV:2     Fahrenheit
AV:3     Fahrenheit
AV:4    Temperature setpoint of the discharge air while in cooling
mode
Fahrenheit
AV:5    Minimum on time setpoint for compressor(s) Seconds
AV:6   󰀨 󰀨 Seconds
AV:7   
Delay
Interstage on delay setpoint when unit has more than one
compressor stage
Seconds
AV:8   󰀨
Delay
󰀨
compressor stage
Seconds
AV:9    

Fahrenheit
AV:10    

Fahrenheit
AV:11    

Fahrenheit
AV:12    

Fahrenheit
AV:13   Occupied Heating Setpoint Heating Mode Enable Setpoint when space is occupied Fahrenheit
AV:14   Unoccupied Heating Setpoint Heating Mode Enable Setpoint when space is unoccupied Fahrenheit
AV:15   Supply Heating Setpoint Temperature setpoint of the discharge air while in heating
mode
Fahrenheit
AV:16   Space Heating Hi Reset 
supply reset control in Heating Mode
Fahrenheit
AV:17   Space Heating Lo Reset 
supply reset control in Heating Mode
Fahrenheit
AV:18   Supply Heating Hi Reset 
supply reset control in Heating Mode
Fahrenheit
AV:19   Supply Heating Lo Reset 
supply reset control in Heating Mode
Fahrenheit
AV:20   Dehum Enable Setpoint 
setpoint
Relative
Humidity
AV:21   Degrees Fahrenheit that the supply air must be under

Fahrenheit
AV:22   Supply Fan Maximum
Percentage
Maximum allowed output for a variable speed supply fan Percent
AV:23   Supply Fan Minimum
Percentage
Minimum allowed output for a variable speed supply fan Percent
AV:24  󰀨 󰀨 Fahrenheit
AV:25  󰀨 󰀨 Fahrenheit
AV:26  󰀨 󰀨 Fahrenheit
Table 1-16: BACnet
®
MS/TP and IP Parameter Analog Values
BACnet
®
MS/TP AND IP PARAMETERS
BACnet
®
MS/TP and IP Analog Values