2-16
Pioneer Gold 3.00 Controller Technical Guide
SETPOINTS
Values
Water Valve Opening Delay
This is the amount of time that the Water Valve needs
to be open before Compressor operation is allowed.
Space Sensor Maximum Setpoint Offset
This setpoint limits how much the user can adjust
the Cooling and Heating setpoints above and
Range: +/- 10°F
Sensor Calibrations
• Space Temperature, Supply Temperature and
Space Humidity Sensor Calibrations: You can adjust
the offset temperature when the sensor is reading
incorrectly. Enter a positive value to raise the reading
Range: +/- 20°F
User Occupancy Override Time
This setpoint allows the user to adjust the occupancy
override time for the Remote Touchscreen Temperature
Range: 30-480 minutes. Entering 0 will disable the
override.