DescriptionTerminal
Memory unit connectionX205
1)
0 = Acceleration/deceleration ramps defined by parameters 23.12/23.13 in use.
1 = Acceleration/deceleration ramps defined by parameters 23.14/23.15 in use.
2)
Constant speed 1 is defined by parameter 22.26.
3)
The DIIL input is configured to stop the unit when the input signal is removed. This input does not have a SIL or PL
classification.
4)
Total load capacity of these outputs is 4.8 W (200 mA at 24 V) minus the power taken by DIO1 and DIO2.
5)
Current [0(4)…20 mA,
R
in
= 100 ohm] or voltage [0(2)…10 V,
R
in
> 200 kohm] input selected by switch AI1. Change
of setting requires reboot of control unit.
6)
Current [0(4)…20 mA,
R
in
= 100 ohm] or voltage [0(2)…10 V,
R
in
> 200 kohm] input selected by switch AI2. Change
of setting requires reboot of control unit.
Control units of the drive 87