Note: The illustration shows the terminal block X20 of the charge post and the
connections treated in this section.
1. Prepare ferrules for the wires that are mentioned below. Refer to section 11.2.
2. Connect these wires from the power cabinet:
Wires from the power
cabinet
Connect to terminal Terminal name
(A) Ground wire or shield
mesh
X20-1 PE
(B) IL IN 1 X20-2 Interlock OUT
(C) IL OUT 1 X20-3 Interlock IN
(D) DC guard A1 X20-9 DC guard signal
(E) DC guard A1 GND X20-10 DC guard GND
Note: The colors of the cables can be different in your equipment.
The colors in the illsutration are used to clarify the explanation and to
distinguish the different cables.
8.6 Connect the optical CAN cable
Note: The Rx and Tx lines must be swapped between the charge the post
and the power cabinet.
Note: For a detailed overview of all electrical connections, refer to
section 12.20.
Preliminary requirements
• Optical CAN cable. Refer to
section 12.19.6
• Cable tie
•
Electrical installation of the charge post
9AKK107992A6488-EN | 004 59