EasyManua.ls Logo

ABB NETA-21 - Page 97

ABB NETA-21
196 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Devices 97
Modbus/TCP settings
The figure below shows the Interface settings dialog box of the Modbus/TCP gateway tab.
32-bit word order is a drop-down list for selecting the most or least significant word
order for 32-bit values. There are 2 options:
Low-high
High-low
Auto nodes RW-flag is a drop-down list for enabling or disabling write access. There
are 2 options:
Read-only
Read-write
Auto write IP address is a text box where the IP address of the Modbus/TCP master
can be specified.
Auto write netmask is a text box where the netmask for Modbus/TCP master IP
address can be specified.
Firewall / allowed on shows the network interfaces on which Modbus/TCP gateway
access is enabled. Changes can be done in Settings -> Network services ->
Firewall settings.
Firewall / denied on shows the network interfaces on which Modbus/TCP gateway
access is disabled. Changes can be done in Settings -> Network services ->
Firewall settings.
Timeout in milliseconds is a text box where the user can specify the maximum
waiting time for a response given to an individual Modbus/TCP request. If the
response hasn't arrived in the allotted time, Modbus error 0x06 - Slave Device Busy
is sent back to the master.
When the master's request contains a range of values, the timeout is applied to each value
separately.

Table of Contents

Other manuals for ABB NETA-21

Related product manuals