Name Type Values (Range) Unit Description
AI_RANGE7 Enum 0=normal
1=high
2=low
3=high-high
4=low-low
RTD input, Connectors
15-16-12c, range
AI_DB8 FLOAT32 -10000.0...10000
.0
RTD input, Connectors
17-18-12c, reported
value
AI_RANGE8 Enum 0=normal
1=high
2=low
3=high-high
4=low-low
RTD input, Connectors
17-18-12c, range
3.12 GOOSE function blocks
GOOSE function blocks are used for connecting incoming GOOSE data to
application. They support BOOLEAN, Dbpos, Enum, FLOAT32, INT8 and INT32
data types.
Common signals
The VALID output indicates the validity of received GOOSE data, which means in
case of valid, that the GOOSE communication is working and received data quality
bits (if configured) indicate good process data. Invalid status is caused either by
bad data quality bits or GOOSE communication failure. See IEC 61850
engineering guide for details.
The OUT output passes the received GOOSE value for the application. Default
value (0) is used if VALID output indicates invalid status. The IN input is defined
in the GOOSE configuration and can always be seen in SMT sheet.
Settings
The GOOSE function blocks do not have any parameters available in LHMI or
PCM600.
3.12.1 GOOSERCV_BIN function block
3.12.1.1 Function block
GUID-44EF4D6E-7389-455C-BDE5-B127678E2CBC V1 EN
Figure 30: Function block
1YHT530004D05 D Section 3
Basic functions
615 series 97
Technical Manual

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB REF615 L and is the answer not in the manual?

ABB REF615 L Specifications

General IconGeneral
TypeFeeder Protection Relay
Rated Frequency50/60 Hz
WeightApprox. 1.5 kg
Communication ProtocolsIEC 61850, Modbus RTU, DNP3
Protection FunctionsOvercurrent, Earth fault, Thermal overload, Under/Over voltage, Under/Over frequency
EnclosureIP20

Related product manuals