Figure 426: Operating effect of the
BLOCK
input when the selected blocking
mode is "Freeze timer"
If the BLOCK input is activated when the operate timer is running, as described in
Figure 426, the timer is frozen during the time BLOCK remains active. If the timer
input is not active longer than specified by the Reset delay time setting, the operate
timer is reset in the same way as described in
Figure 424, regardless of the BLOCK
input .
The selected blocking mode is "Freeze timer".
11.2 Current based inverse definite minimum time
characteristics
11.2.1 IDMT curves for overcurrent protection
The inverse-time modes, the operation time depends on the momentary value of the
current: the higher the current, the faster the operation time. The operation time
calculation or integration starts immediately when the current exceeds the set Start
value and the START output is activated.
Section 11 1YHT530004D05 D
General function block features
794 615 series
Technical Manual