4.2.5.7 Settings
Table 326: HAEFPTOC Group settings
Parameter Values (Range) Unit Step Default Description
Start value 0.05...5.00 xIn 0.01 0.10 Start value
Time multiplier 0.05...15.00 0.01 1.00 Time multiplier in IEC/ANSI IDMT curves
Operate delay time 100...200000 ms 10 600 Operate delay time
Minimum operate time 100...200000 ms 10 500 Minimum operate time for IDMT curves
Operating curve type 1=ANSI Ext. inv.
2=ANSI Very inv.
3=ANSI Norm. inv.
4=ANSI Mod. inv.
5=ANSI Def. Time
6=L.T.E. inv.
7=L.T.V. inv.
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv.
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
15=IEC Def. Time Selection of time delay curve type
Type of reset curve 1=Immediate
2=Def time reset
3=Inverse reset
1=Immediate Selection of reset curve type
Enable reference use 0=False
1=True
0=False Enable using current reference from
other IEDs instead of stand-alone
Table 327: HAEFPTOC Non group settings
Parameter
Values (Range) Unit Step Default Description
Operation 1=on
5=off
1=on Operation Off / On
Reset delay time 0...60000 ms 10 20 Reset delay time
Curve parameter A 0.0086...120.0000 28.2000 Parameter A for customer programmable
curve
Curve parameter B 0.0000...0.7120 0.1217 Parameter B for customer programmable
curve
Curve parameter C 0.02...2.00 2.00 Parameter C for customer
programmable curve
Curve parameter D 0.46...30.00 29.10 Parameter D for customer
programmable curve
Curve parameter E 0.0...1.0 1.0 Parameter E for customer programmable
curve
1YHT530004D05 D Section 4
Protection functions
615 series 343
Technical Manual