11.3 Voltage based inverse definite minimum time
characteristics
11.3.1 IDMT curves for overvoltage protection
In inverse-time modes, the operate time depends on the momentary value of the
voltage, the higher the voltage, the faster the operate time. The operate time
calculation or integration starts immediately when the voltage exceeds the set value
of the Start value setting and the START output is activated.
The OPERATE output of the component is activated when the cumulative sum of
the integrator calculating the overvoltage situation exceeds the value set by the
inverse time mode. The set value depends on the selected curve type and the setting
values used. The user determines the curve scaling with the Time multiplier setting.
The Minimum operate time setting defines the minimum operate time for the IDMT
mode, that is, it is possible to limit the IDMT based operate time for not becoming
too short. For example:
1YHT530004D05 D Section 11
General function block features