8.2.1.4 Sampling frequencies
The sampling frequency of the disturbance recorder analog channels depends on
the set rated frequency. One fundamental cycle always contains the amount of
samples set with the Storage rate parameter. Since the states of the binary channels
are sampled once per task execution of the disturbance recorder, the sampling
frequency of binary channels is 400 Hz at the rated frequency of 50 Hz and 480 Hz
at the rated frequency of 60 Hz.
Table 574: Sampling frequencies of the disturbance recorder analog channels
Storage rate
(samples per
fundamental
cycle)
Recording
length
Sampling
frequency of
analog
channels, when
the rated
frequency is 50
Hz
Sampling
frequency of
binary
channels, when
the rated
frequency is 50
Hz
Sampling
frequency of
analog
channels, when
the rated
frequency is 60
Hz
Sampling
frequency of
binary
channels, when
the rated
frequency is 60
Hz
32 1* Record
length
1600 Hz 400 Hz 1920 Hz 480 Hz
16 2* Record
length
800 Hz 400 Hz 960 Hz 480 Hz
8 4 * Record
length
400 Hz 400 Hz 480 Hz 480 Hz
8.2.1.5 Uploading of recordings
The IED stores COMTRADE files to the C:\COMTRADE\ folder. The files can be
uploaded with the PCM tool or any appropriate computer software that can access
the C:\COMTRADE\ folder.
One complete disturbance recording consists of two COMTRADE file types: the
configuration file and the data file. The file name is the same for both file types.
The configuration file has .CFG and the data file .DAT as the file extension.